Miscellaneous action | | | 9/3/2009 | | DONE |
|
|
|
Fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 8/31/2009 | 9/1/2009 | 9/2/2009 | A | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 8/26/2009 | 8/27/2009 | 8/28/2009 | P | PART |
Forrest France
|
|
|
Continued inspection completed 8/27 afternoon and evening by F. France and B. Johnson for the remainder permit work including correction items. Room signage, building map, program changes, and breaker lock okayed, vesda faults tested okay, signals at main FACP verified, low air supervisory signals tested, alert and alarm signals sent/recieved, transport times at several systems measured and found to be under max. time limits, systems 22, 23, 24, 25 and 17 passed, system 18 failed. Continued testing while system 18 repaired. Sequence of operation passed for the freezer systems including rack systems 26,27,28,29, and area served. Repairs at system 18 modules and VESDA completed and retested okay per B. Johnson. Final pending NFPA 72 record of inspection and testing and record of completion documents for signature.
|
INSP-Final Inspection | 8/26/2009 | 8/26/2009 | 8/28/2009 | P | NR |
Forrest France
|
|
|
Items noted during a lengthy inspection completed 8/26 morning and afternoon include failure to initiate alarm condition at the first three single interlock systems checked 16, 19, and 20, missing labels at some VESDA units, led lamps do not illuminate at some modules on trouble condition at the freezer vesdas, noted end cap locations at the floor level have not been installed per design-caps are now at the ceiling deck at all systems. After program changes made while on site, alarm condition for the single interlock system 16 rechecked and found to incorrectly initiate solenoid release for all fourteen single and double interlock systems, overspacing of detectors at systems 16,17,18 and 21 okayed after repairs made, continued testing after more program changes showed systems 19, 20, 21, and 16 functioned correctly.
|
INSP-Final Inspection | 8/24/2009 | 8/25/2009 | 8/25/2009 | A | FAIL |
Forrest France
|
|
|
Deficient items found during the first three hours of inspection include missing NFPA 72 Record of Inspection and Testing with a copy of supervising station signals report per plan review note #3, missing signage per review note #1, provide a lock and label at the power circut breaker to the panel, A/C power off failed to report to the main FACP-see note #5, per details on approved plans 90 deg. ells to be avoided and 6" to 10" clearance to be provided at each side of the freezer wall to avoid ice plugs-noted significant frosting at these locations, the first VESDA fault at system 28 did not report, plans incorrectly show location of system 27, south line of smoke detection at systems 16,17, and 18 are overspaced-see fire code review note #13, provide a building map at the releasing panel indicating floorplan layout and locations of all initiating devices-see plan review note #15, repairs underway at VESDA system 29.
|
Plan assigned to (Stephanie) | 8/20/2009 | | 8/24/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
8/24/2009 08:50:46 SLC - activity updated through activity FIRA24 from case FIR09-00296.
|
1st review completed | | | 8/24/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 8/24/2009 | | 8/24/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 8/24/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Permit Ready to Issue | | | 8/24/2009 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/24/2009 | | 8/24/2009 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 8/24/2009 | | DONE |
|
|
|
Called Joe with Allied General and told him that permit is ready & fees due///8-24-09 @ 12:25///BAS
|
(F) Reprint permit | | | 8/24/2009 | | DONE |
Tisha Gallop
|
|
|
|
CHANGE STATUS TO (ISS) | | | 8/24/2009 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/20/2009 | | |
|
|
|
Rec'd two copies of plans
|
Issue and Print Permit | | | 5/22/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Plan assigned to (Stephanie) | 5/8/2009 | | 5/21/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
5/21/2009 14:19:49 SLC - activity updated through activity FIRA24 from case FIR09-00296.
|
Alarm Plan Check | 5/21/2009 | | 5/21/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See review comments and redlines (preaction releasing system)
|
PLANS TAKEN FRONT DESK ALARM | | | 5/21/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Inspection Record Card- Fire | 5/21/2009 | | 5/21/2009 | | DONE |
|
|
|
|
Telephone call | | | 5/21/2009 | | DONE |
|
|
|
t/c w ken webster at ###-#### - permit ready - no fees due
|
Permit Ready to Issue | | | 5/21/2009 | | DONE |
|
|
|
|
Application received | | | 5/8/2009 | | |
|
|
|
|