Miscellaneous action | | | 2/26/2010 | | DONE |
|
|
|
fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 2/4/2010 | 2/5/2010 | 2/5/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 1/15/2010 | 1/15/2010 | 1/15/2010 | P | FAIL |
Troy Cobbley
|
|
|
Could not get access to the fire alarm panel due to the room being locked. WIll have to reschedule.
|
INSP-Final Inspection | 6/19/2009 | 6/25/2009 | 6/25/2009 | P | FAIL |
Forrest France
|
|
|
AES battery and antenna failure did not indicate trouble condition at the FACP. Remainder of permit work tested okay.
|
Plan assigned to (Stephanie) | 5/13/2009 | | 5/27/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
5/27/2009 10:54:14 SLC - activity updated through activity FIRA24 from case FIR09-00320.
|
Alarm Plan Check | 5/27/2009 | | 5/27/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 5/27/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Permit Ready to Issue | | | 5/27/2009 | | |
|
|
|
|
Inspection Record Card- Fire | 5/27/2009 | | 5/27/2009 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 5/27/2009 | | DONE |
Barbara Stitt
|
|
|
Called Ken Webster and told him that permit is readu & fees due///5-27-09 @11:51am BAS
|
Issue and Print Permit | | | 5/27/2009 | | DONE |
|
|
|
|
Application received | | | 5/13/2009 | | |
|
|
|
|