Miscellaneous action | | | 2/8/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 1/5/2011 | 1/5/2011 | 1/6/2011 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 12/28/2010 | 12/28/2010 | 12/28/2010 | P | CANC |
Troy Cobbley
|
|
|
To be rescheduled with the two AES permits on Phillippi
|
FIR-Aging Inspection | 12/8/2010 | 12/8/2010 | 12/16/2010 | | NR |
Troy Cobbley
|
|
|
Per Brett he is waiting on a points map for the facp and then will call in the inspection.
|
INSP-Final Inspection | 3/16/2010 | 3/16/2010 | 3/16/2010 | P | FAIL |
Troy Cobbley
|
|
|
The dedicated circuit has been provided but the map and NFPA 72 forms are still needed.
|
INSP-Final Inspection | 10/28/2009 | 10/30/2009 | 10/30/2009 | A | FAIL |
Troy Cobbley
|
|
|
Provide dedicated circuit as per the review comments and NFPA 72 and provide a map at the facp as discussed.
|
INSP-Final Inspection | 9/23/2009 | 9/24/2009 | 9/24/2009 | P | CANC |
Troy Cobbley
|
|
|
No actual inspection was performed. I spoke to Tim on the phone and we discussed the IFC 903.4 requirement for the sprinkler control valves to be supervised by the fire alarm panel. The inspection is to be rescheduled.
|
Issue and Print Permit | | | 8/31/2009 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (Stephanie) | 5/13/2009 | | 8/24/2009 | | DONE |
Barbara Stitt
|
|
|
8/24/2009 12:33:32 SLC - activity updated through activity FIRA24 from case FIR09-00321.
|
Alarm Plan Check | 8/24/2009 | | 8/24/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 8/24/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Permit Ready to Issue | | | 8/24/2009 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/24/2009 | | 8/24/2009 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 8/24/2009 | | DONE |
|
|
|
Called and left message that permit is ready & fees due///8-24-09 @ 1:00pm BAS
|
Plan resubmittals received | | | 8/20/2009 | | |
Stephanie L. Cobbley
|
|
|
Rec'd two copies of plans and application
|
Miscellaneous action | | | 6/2/2009 | | DONE |
Tisha Gallop
|
|
|
picked up denied plans
|
Alarm Plan Check | 5/27/2009 | | 5/27/2009 | | FAIL |
Stephanie L. Cobbley
|
|
|
Review comments faxed to contractor. Denied plans available at front counter for customer pick up.
|
Telephone call | | | 5/27/2009 | | DONE |
|
|
|
Called Bret to let him know the plans are being denied and to expect the faxed review comments.
|
1st review completed | | | 5/27/2009 | | DONE |
|
|
|
|
Application received | | | 5/13/2009 | | DONE |
Barbara Stitt
|
|
|
|