Miscellaneous action | | | 12/21/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 12/2/2010 | 12/8/2010 | 12/8/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
FIR-Aging Inspection | 11/10/2010 | 11/10/2010 | 11/17/2010 | | NR |
Troy Cobbley
|
|
|
Mike stated that this should be set up for inspection the week after Thanksgiving.
|
INSP-Final Inspection | 6/30/2010 | 6/30/2010 | 7/1/2010 | P | FAIL |
Troy Cobbley
|
|
|
There is no independant supervisory signal being reported. The existing facp is capable of this function per the Pyrotronics vendor. This capability will need to be installed and tested prior to a final sign off. The technician and I discussed the issue.
|
Telephone call | | | 4/19/2010 | | DONE |
|
|
|
Spoke to Mike regarding the project status. He indicated he would be calling in for a final.
|
FIR-Aging Inspection | 9/14/2009 | 9/14/2009 | 9/14/2009 | | NR |
Troy Cobbley
|
|
|
wip
|
Issue and Print Permit | | | 6/11/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Miscellaneous action | | | 6/4/2009 | | DONE |
Tisha Gallop
|
|
|
original copy of field set of plan was issued to wrong contractor and lost. Per Scott A. made copy of Office Copy and redlined to be Field Copy.
|
Inspection Record Card- Fire | 6/4/2009 | | 6/4/2009 | | DONE |
Tisha Gallop
|
|
|
|
Inspection Record Card- Fire | 6/1/2009 | | 6/1/2009 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 6/1/2009 | | DONE |
|
|
|
|
Telephone call | | | 6/1/2009 | | DONE |
|
|
|
Called and left message that permit is ready///6-1-09 @ 9:50am BAS
|
Issue and Print Permit | | | 6/1/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 5/27/2009 | | 5/29/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
5/29/2009 10:28:32 SLC - activity updated through activity FIRA24 from case FIR09-00342.
|
Alarm Plan Check | 5/29/2009 | | 5/29/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See review comments and redlines
|
PLANS TAKEN FRONT DESK ALARM | | | 5/29/2009 | | DONE |
|
|
|
Approved redlined documentation available at front counter
|
Application received | | | 5/27/2009 | | |
|
|
|
|