Miscellaneous action | | | 10/1/2009 | | DONE |
|
|
|
Fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 9/3/2009 | 9/4/2009 | 9/4/2009 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The diffuser has been relocated
|
INSP-Final Inspection | 8/24/2009 | 8/25/2009 | 8/25/2009 | A | FAIL |
Troy Cobbley
|
|
|
The smoke detector closest to the entry door needs to be relocated atleast 3' from the supply register and test for functionality. All other items tested ok. The operation sequence for the releasing panel had to be changed as I waited so that only one initiating device is required to trip the pre-action system.
|
INSP-Alarm Testing | 8/24/2009 | 8/24/2009 | 8/24/2009 | A | DONE |
Troy Cobbley
|
|
|
Inspection was actually for a telephone conference.
|
Issue and Print Permit | | | 6/9/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 5/29/2009 | | 6/3/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
6/3/2009 08:29:00 SLC - activity updated through activity FIRA24 from case FIR09-00343.
|
Alarm Plan Check | 6/3/2009 | | 6/3/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 6/3/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Inspection Record Card- Fire | 6/3/2009 | | 6/3/2009 | | DONE |
|
|
|
|
Telephone call | | | 6/3/2009 | | DONE |
|
|
|
left vm for charlie at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 6/3/2009 | | DONE |
|
|
|
|
Case Summary | | | 5/29/2009 | | DONE |
|
|
|
|
Application received | | | 5/29/2009 | | |
|
|
|
|