Miscellaneous action | | | 1/5/2010 | | DONE |
Tim Frost
|
|
|
Plans taken to scanning.
|
INSP-Final Inspection | 11/24/2009 | 11/24/2009 | 11/25/2009 | A | PASS |
Forrest France
|
|
|
Final walkthrough passed, correction items are finished, fire sprinkler permit finaled.
|
INSP-Final Inspection | 11/10/2009 | 11/12/2009 | 11/12/2009 | A | PART |
Forrest France
|
|
|
Noted racking at the scan room has been lowered, remainder of c/n items are complete, final pending installation of missing ceiling tile at several locations in the main office.
|
INSP-Final Inspection | 9/15/2009 | 9/16/2009 | 9/17/2009 | A | PART |
Forrest France
|
|
|
TOC approved.
|
INSP-Final Inspection | 8/20/2009 | 8/20/2009 | 8/21/2009 | P | PART |
Forrest France
|
|
|
Reinspection for C/N item at system 31 perishables office passed, noted items at system 14 main office include missing ceiling tiles and escutcheons at some locations, new shelving installed at the "scan room" blocks coverage and may affect room hazard classification, two locations above the office exit doors south side are lacking coverage as the adjacent upright heads in the shift exchange are blocked by an elevation change.
|
INSP-Sprinkler Rough-in | 6/17/2009 | 6/18/2009 | 6/18/2009 | A | PART |
Forrest France
|
|
|
System 12 office area overhead installation is approved for cover as noted on plans with the exception of two heads to be relocated due to blockage/overspaced coverage.
|
INSP-Sprinkler Rough-in | 6/8/2009 | 6/9/2009 | 6/9/2009 | A | PART |
Forrest France
|
|
|
See approved plans for locations circled and marked with today's date okayed for sheetrock ceiling cover, noted one obstructed head by a light fixture to be relocated at the women's restroom.
|
Plan assigned to (Tim) | 6/5/2009 | | 6/8/2009 | | DONE |
Tim Frost
|
|
|
6/8/2009 11:18:34 TRF - activity updated through activity FIRA22 from case FIR09-00363.
|
Sprinkler Plan Check | 6/8/2009 | | 6/8/2009 | | PASS |
Tim Frost
|
|
|
Please, see FIR09-00033 for complete details on this facility. The office area is approved, however, there are still unresolved issues regarding the remaining portion of this facilitly
|
1st review completed | | | 6/8/2009 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/8/2009 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 6/8/2009 | | 6/8/2009 | | DONE |
|
|
|
|
Telephone call | | | 6/8/2009 | | DONE |
|
|
|
tim frost called and told jeff the permit was ready
|
Permit Ready to Issue | | | 6/8/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/8/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Application received | | | 6/5/2009 | | |
|
|
|
|
Case Summary | | | 6/5/2009 | | DONE |
|
|
|
|