INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 | A | PASS |
Forrest France
|
|
|
Final walkthrough passed, fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in | 7/21/2009 | 7/22/2009 | 7/22/2009 | P | PART |
Forrest France
|
|
|
Noted corrections verified for completion, overhead modifications okay for cover.
|
INSP-Sprinkler Rough-in | 7/20/2009 | 7/21/2009 | 7/21/2009 | P | FAIL |
Forrest France
|
|
|
Pendent head at the storage room is overspaced, two hangers at office 412 are beyond max. spacing to heads on systems over 100 psi. See red line annotations on stamped plan set and circled items # 19 and 22 on FP1 under general notes for details.
|
INSP-Sprinkler Rough-in | 7/20/2009 | 7/20/2009 | 7/20/2009 | P | DEFR |
Forrest France
|
|
|
Could we geet this around 3ish, Ryan is the contact at ###-####. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus
|
Plan assigned to (Tim) | 6/18/2009 | | 6/18/2009 | | DONE |
Tim Frost
|
|
|
6/18/2009 10:58:59 TRF - activity updated through activity FIRA22 from case FIR09-00370.
|
Sprinkler Plan Check | 6/18/2009 | | 6/18/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/18/2009 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 6/18/2009 | | 6/18/2009 | | DONE |
|
|
|
|
Telephone call | | | 6/18/2009 | | DONE |
|
|
|
left message w darcy for cam hess at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 6/18/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/18/2009 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (Tim) | 6/10/2009 | | 6/16/2009 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 6/15/2009 | | 6/15/2009 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 6/15/2009 | | DONE |
Tim Frost
|
|
|
|
Meeting | | | 6/15/2009 | | DONE |
Tim Frost
|
|
|
Faxed review comments
|
Telephone call | | | 6/15/2009 | | DONE |
|
|
|
t/c w cam hess at ###-#### - permit denied - needs to be picked up and resubmitted
|
Plan resubmittals received | | | 6/15/2009 | | |
Tim Frost
|
|
|
Rec'd 4 copies of plans- taken to Tim
|
Application received | | | 6/10/2009 | | |
|
|
|
|