Miscellaneous action | | | 12/3/2009 | | DONE |
|
|
|
FA plans taken to records for scanning
|
INSP-Final Inspection | 11/12/2009 | 11/12/2009 | 11/12/2009 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled, corrections finished.
|
INSP-Sprinkler Rough-in/Hydro | 9/15/2009 | 9/16/2009 | 9/17/2009 | A | PART |
Forrest France
|
|
|
TOC approved.
|
INSP-Final Inspection | 9/14/2009 | 9/14/2009 | 9/14/2009 | P | PART |
Forrest France
|
|
|
Inspection date is 9/15 as previously discussed.
|
INSP-Final Inspection | 9/9/2009 | 9/9/2009 | 9/9/2009 | P | PART |
Forrest France
|
|
|
Corrections verified for completion, fire alarm system testing passed, XP strobes at the fuel station area are not installed.
|
INSP-Final Inspection | 9/8/2009 | 9/8/2009 | 9/8/2009 | P | FAIL |
Forrest France
|
|
|
Seven manual pull stations are mounted too high-see fire code review note #9, two 75cd notification appliances are overspaced at the return bay, one 110cd appliance is overspaced per install and red lined note on stamped plan set- see note #1, main drain vavle at the sprinkler riser need not be supervised, explosion proof strobes at the fuel bay are missing, overspaced notification per plan review annotations at the return bay, provide "NFPA 72 Record of Inspection and Testing" per note #3, provide a lock and label at the panel circut breaker-note #8. No further testing completed at this time until repairs are finished.
|
INSP-Final Inspection | 9/4/2009 | 9/4/2009 | 9/8/2009 | P | NR |
Forrest France
|
|
|
brian Phone #: ###-####
|
INSP-Final Inspection | 9/3/2009 | 9/3/2009 | 9/8/2009 | P | NR |
Forrest France
|
|
|
Incompleted work on 9/3.
|
Inspection Record Card- Fire | 6/25/2009 | | 6/25/2009 | | DONE |
|
|
|
|
Telephone call | | | 6/25/2009 | | DONE |
|
|
|
t/c w lori at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 6/25/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/25/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 6/18/2009 | | 6/24/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
6/24/2009 13:38:21 SLC - activity updated through activity FIRA24 from case FIR09-00386.
|
Alarm Plan Check | 6/24/2009 | | 6/24/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 6/24/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Application received | | | 6/18/2009 | | |
|
|
|
|