Miscellaneous action | | | 7/17/2009 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 7/7/2009 | 7/7/2009 | 7/7/2009 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Plan assigned to (Stephanie) | 6/22/2009 | | 6/24/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
6/24/2009 09:29:49 SLC - activity updated through activity FIRA24 from case FIR09-00392.
|
Telephone call | | | 6/24/2009 | | DONE |
|
|
|
Spoke with Charlie B. at SimplexGrinnell regarding Poly rooms 187 & 188. They are shown without notification, however Polygraph Room 189 has a visual device. I asked Charlie if there was a reason 187 & 188 did not have notification. He stated that room 189 will be constantly manned while rooms 187 & 188 are occupied and that those rooms are more of an 'interrogation' type of atmosphere. I agreed that notification could be ommited as long as room 189 is manned as stated above. I let him know that if, upon field inspection, it proves otherwise, notification will need to be added.
|
Alarm Plan Check | 6/24/2009 | | 6/24/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
quick permit, no written comments
|
PLANS TAKEN FRONT DESK ALARM | | | 6/24/2009 | | DONE |
|
|
|
Approved, redlined plans available at front counter
|
Inspection Record Card- Fire | 6/24/2009 | | 6/24/2009 | | DONE |
|
|
|
|
Telephone call | | | 6/24/2009 | | DONE |
|
|
|
t/c w charlie bayne at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 6/24/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/24/2009 | | DONE |
|
|
|
|
Application received | | | 6/22/2009 | | |
|
|
|
|