INSP-Final Inspection | 9/23/2009 | 9/23/2009 | 9/24/2009 | P | PASS |
Forrest France
|
|
|
Correction notice item completed, fire sprinkler permit okay for final.
|
INSP-Final Inspection | 9/21/2009 | 9/22/2009 | 9/22/2009 | A | FAIL |
Forrest France
|
|
|
Millwork at the reception "area 102" obstructs sprinkler coverage, remainder of install passed, previous C/N items are finished.
|
INSP-Sprinkler Rough-in | 9/1/2009 | 9/1/2009 | 9/2/2009 | A | NR |
Forrest France
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 8/10/2009 | 8/11/2009 | 8/11/2009 | A | FAIL |
Forrest France
|
|
|
New pendent heads installed at the office area do not match approved plans and submittals, must also be quick response type per IFC 2006 903.3.2 (3).
|
INSP-Sprinkler Rough-in/Hydro | 7/23/2009 | 7/24/2009 | 7/24/2009 | P | PART |
Forrest France
|
|
|
See stamped plan set on site for locations inspected today and approved for cover at the sheetrock ceilings including the 1st floor lobby.
|
Plan assigned to (Tim) | 6/23/2009 | | 6/24/2009 | | DONE |
Tim Frost
|
|
|
6/24/2009 08:52:56 TRF - activity updated through activity FIRA22 from case FIR09-00394.
|
Sprinkler Plan Check | 6/24/2009 | | 6/24/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 6/24/2009 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/24/2009 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 6/24/2009 | | 6/24/2009 | | DONE |
|
|
|
|
Telephone call | | | 6/24/2009 | | DONE |
|
|
|
t/c w jeff anderson at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 6/24/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/24/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Case Summary | | | 6/23/2009 | | DONE |
|
|
|
|
Application received | | | 6/23/2009 | | |
|
|
|
|