Miscellaneous action | | | 9/3/2009 | | DONE |
|
|
|
Fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 8/14/2009 | 8/17/2009 | 8/18/2009 | A | PASS |
Forrest France
|
|
|
Correction notice item verified for compliance, functional testing passed, per NFPA 72 2007 Handbook 6.8.1.1 actuation time at the relocated manual pull station is acceptable.
|
INSP-Final Inspection | 8/13/2009 | 8/14/2009 | 8/14/2009 | A | FAIL |
Forrest France
|
|
|
Existing manual pull station at the south exit vestibule needs relocated to no higher than 48" AFF to the operable part, location of new notification devices apppears acceptable, will test relocated MP and new a/v's at next site visit.
|
Issue and Print Permit | | | 7/7/2009 | | DONE |
|
|
|
|
1st review completed | | | 7/6/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 6/30/2009 | | 7/6/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
7/6/2009 13:54:18 SLC - activity updated through activity FIRA24 from case FIR09-00406.
|
Alarm Plan Check | 7/6/2009 | | 7/6/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 7/6/2009 | | DONE |
|
|
|
Approved redlined drawings available at front counter
|
Inspection Record Card- Fire | 7/6/2009 | | 7/6/2009 | | DONE |
|
|
|
|
Telephone call | | | 7/6/2009 | | DONE |
|
|
|
t/c w jason minnick at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/6/2009 | | DONE |
|
|
|
|
Application received | | | 6/30/2009 | | |
|
|
|
|