Miscellaneous action | | | 2/26/2010 | | DONE |
|
|
|
fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 1/27/2010 | 1/28/2010 | 1/28/2010 | P | PASS |
Forrest France
|
|
|
Fire alarm permit work passed inspection after corrections made while on site to amend account information to include correct zones and descriptors for signals transmitted including trouble and supervisory conditions.
|
INSP-Final Inspection | 8/20/2009 | 8/20/2009 | 8/20/2009 | P | FAIL |
Troy Cobbley
|
|
|
I arrived on site and was notified by TIm that the netcom rating was not a 5 or less. No inspection was not continued.
|
INSP-Final Inspection | 7/28/2009 | 7/31/2009 | 7/30/2009 | A | CANC |
Forrest France
|
|
|
Tim Christopherson Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|
INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/28/2009 | P | CANC |
Forrest France
|
|
|
Tim Christopherson Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|
Issue and Print Permit | | | 7/13/2009 | | DONE |
|
|
|
|
1st review completed | | | 7/10/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 6/30/2009 | | 7/10/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
7/10/2009 11:00:05 SLC - activity updated through activity FIRA24 from case FIR09-00410.
|
Alarm Plan Check | 7/10/2009 | | 7/10/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 7/10/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 7/10/2009 | | 7/10/2009 | | DONE |
|
|
|
|
Telephone call | | | 7/10/2009 | | DONE |
|
|
|
t/c w rose at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/10/2009 | | DONE |
|
|
|
|
Application received | | | 6/30/2009 | | |
|
|
|
|