INSP-Final Inspection | 2/23/2010 | 2/23/2010 | 2/23/2010 | P | PASS |
Forrest France
|
|
|
UG fire supply line permit work okay for final status per activity notes and overhead system testing for project related FIR's.
|
CHANGE STATUS TO (ISS) | | | 1/5/2010 | | DONE |
Barbara Stitt
|
|
|
No resubmittals here changed back to issue status 1-5-10 BAS
|
Plan resubmittals received | | | 12/18/2009 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Tim) | 12/18/2009 | | 12/18/2009 | | DONE |
Tim Frost
|
|
|
|
INSP-Alarm Testing | 12/10/2009 | 12/11/2009 | 12/11/2009 | P | CANC |
Troy Cobbley
|
|
|
Wrong inspection type called in.
|
INSP-Supply line flush | 12/2/2009 | 12/3/2009 | 12/3/2009 | A | PASS |
Troy Cobbley
|
|
|
The underground flush passed.
|
INSP-Sprinkler Rough-in/Hydro | 12/1/2009 | 12/1/2009 | 12/1/2009 | P | PASS |
Troy Cobbley
|
|
|
Underground hydro test passed.
|
INSP-Sprinkler Rough-in | 7/20/2009 | 7/21/2009 | 7/21/2009 | P | PASS |
Troy Cobbley
|
|
|
The 6" underground supply piping is ok to cover.
|
INSP-Sprinkler Rough-in | 7/16/2009 | 7/17/2009 | 7/17/2009 | A | FAIL |
Troy Cobbley
|
|
|
The new 6" underground supply piping does not meet the state requirement of a minumum 4'-6" bury depth. I went over the depth of bury with EKC while on site and contacted Trent with Phoenix Fire. Pipe can not be buried until re-inspected.
|
INSP-Sprinkler Rough-in | 7/16/2009 | 7/16/2009 | 7/16/2009 | P | CANC |
Troy Cobbley
|
|
|
Rescheduled for tomorrow morning due to time constraints today.
|
Permit Ready to Issue | | | 7/9/2009 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/9/2009 | | 7/9/2009 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 7/9/2009 | | DONE |
Barbara Stitt
|
|
|
Called and left message for Trent that permit is ready & fees due///7-9-09 @ 9:15am BAS
|
Issue and Print Permit | | | 7/9/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Plan assigned to (Tim) | 7/7/2009 | | 7/8/2009 | | DONE |
Tim Frost
|
|
|
7/8/2009 14:43:00 TRF - activity updated through activity FIRA22 from case FIR09-00419.
|
Sprinkler Plan Check | 7/8/2009 | | 7/8/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 7/8/2009 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/8/2009 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 7/7/2009 | | |
|
|
|
|