Miscellaneous action | | | 7/28/2010 | | DONE |
|
|
|
FA plans taken to records for scanning.
|
INSP-Final Inspection | 7/21/2010 | 7/22/2010 | 7/22/2010 | A | PASS |
Forrest France
|
|
|
Corrections finished, fire alarm passed inspection. Permit finaled.
|
Telephone call | | | 4/19/2010 | | DONE |
|
|
|
Spoke with Bret regarding the status of the project. He indicated difficulty in obtaining the building map required. He stated he would work on getting that resolved.
|
INSP-Final Inspection | 7/29/2009 | 7/30/2009 | 7/30/2009 | P | FAIL |
Forrest France
|
|
|
RF radio equipment for monitoring must have a NETcon rating of 5 or lower, see fire code review notes item #5 for details. Site testing indicated a NETcon 6.
|
INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 | P | CANC |
Forrest France
|
|
|
Overbooked
|
Issue and Print Permit | | | 7/16/2009 | | DONE |
|
|
|
|
1st review completed | | | 7/15/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 7/13/2009 | | 7/15/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
7/15/2009 14:48:39 SLC - activity updated through activity FIRA24 from case FIR09-00427.
|
Alarm Plan Check | 7/15/2009 | | 7/15/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 7/15/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 7/15/2009 | | 7/15/2009 | | DONE |
|
|
|
|
Telephone call | | | 7/15/2009 | | DONE |
|
|
|
t/c w bret anderson at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/15/2009 | | DONE |
|
|
|
|
Application received | | | 7/13/2009 | | |
|
|
|
|