Miscellaneous action | | | 3/8/2010 | | DONE |
|
|
|
Plans sent to scanning.
|
INSP-Final Inspection | 2/18/2010 | 2/19/2010 | 2/19/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 2/18/2010 | 2/18/2010 | 2/18/2010 | P | FAIL |
Troy Cobbley
|
|
|
Due to time constraits I was unable to complete the entire inspection. The forward flush passed as well as the fire alarm interconnections. Verification of ceiling installation, canopy installation and any possible blocked heads due to light fixtures still needs to be completed.
|
INSP-Sprinkler Rough-in/Hydro | 12/3/2009 | 12/3/2009 | 12/3/2009 | P | PASS |
Troy Cobbley
|
|
|
The sprinkler piping can now be covered.
|
INSP-Sprinkler Rough-in/Hydro | 12/2/2009 | 12/3/2009 | 12/3/2009 | A | PASS |
Troy Cobbley
|
|
|
The overhead piping passed the hydro tests.
|
INSP-Sprinkler Rough-in | 12/1/2009 | 12/2/2009 | 12/2/2009 | P | PART |
Troy Cobbley
|
|
|
Piping is ok to cover except at the top of the vertical risers which will require additional insulation and the voids under both fire places needs filled with insulation as well.
|
INSP-Sprinkler Rough-in | 11/24/2009 | 11/27/2009 | 11/27/2009 | A | PASS |
Troy Cobbley
|
|
|
The previous items on the correction notice have been corrected. The piping still can not be covered until the combustible concealed spaces throughout the facility, including at the fire places have been addressed and the veritical cpvc piping is insulated. These items need to be inspected prior to cover.
|
INSP-Sprinkler Rough-in | 11/23/2009 | 11/24/2009 | 11/24/2009 | A | PART |
Troy Cobbley
|
|
|
All of the attic system was inspected as well as just the east wing of the wet system. In several locations the sidewall heads are too close to one another and once the ceiling is installed may be too close to the ceiling. The contractor needs to contact Tim Frost about changes that could adversely effect the attic system hydraulic calculations. The location of acouple of the upright sprinkler heads need to be modified to provide correct sprinkler coverage. Earthquake bracing needs to be modified so that the "earthquake ears" are not used as discussed.
|
Sprinkler Plan Check | 9/11/2009 | | 9/11/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/11/2009 | | DONE |
Tim Frost
|
|
|
|
Override - Parcel Holds | | | 9/11/2009 | | |
|
|
|
|
Override - Parcel Holds | | | 9/11/2009 | | |
|
|
|
|
Inspection Record Card- Fire | 9/11/2009 | | 9/11/2009 | | DONE |
|
|
|
|
Telephone call | | | 9/11/2009 | | DONE |
|
|
|
t/c w kim at ###-#### - permit ready and fees given
|
Override - Parcel Holds | | | 9/11/2009 | | |
|
|
|
|
Override - Parcel Holds | | | 9/11/2009 | | |
|
|
|
|
Permit Ready to Issue | | | 9/11/2009 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 9/11/2009 | | |
|
|
|
|
Override - Parcel Holds | | | 9/11/2009 | | |
|
|
|
|
Issue and Print Permit | | | 9/11/2009 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/3/2009 | | |
Tim Frost
|
|
|
Rec'd 4 copies of plans and submittal info- taken to Tim F
|
Plan assigned to (Tim) | 7/16/2009 | | 7/20/2009 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 7/20/2009 | | 7/20/2009 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 7/20/2009 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 7/20/2009 | | DONE |
Tim Frost
|
|
|
Emailed review to Matt Kahns
|
Telephone call | | | 7/20/2009 | | DONE |
|
|
|
t/c w bryan johnson at ###-#### - permit denied - needs to be picked up and resubmitted
|
Application received | | | 7/16/2009 | | |
|
|
|
|
Pending Assignment by SAM | 7/16/2009 | | 7/16/2009 | | DONE |
Tisha Gallop
|
|
|
7/16/2009 08:11:38 LEG - activity updated through activity FIRA158 from case FIR09-00440.
|