Miscellaneous action | | | 1/14/2011 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 7/28/2010 | 7/28/2010 | 7/28/2010 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 10/20/2009 | 10/21/2009 | 10/21/2009 | A | PART |
Troy Cobbley
|
|
|
The Phase I sprinkler work is complete except for a couple of ceiling tiles which Darren with HC Company stated he would get installed.
|
INSP-Sprinkler Rough-in/Hydro | 10/13/2009 | 10/14/2009 | 10/14/2009 | A | PASS |
Troy Cobbley
|
|
|
See the city approved plans for the areas marked in red ink where the piping can be covered.
|
Sprinkler Plan Check | 8/6/2009 | | 8/6/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/6/2009 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 8/6/2009 | | 8/6/2009 | | DONE |
|
|
|
|
Telephone call | | | 8/6/2009 | | DONE |
|
|
|
t/c w brodie at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 8/6/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/6/2009 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/5/2009 | | |
Tim Frost
|
|
|
Rec'd 3 copies of plans
|
Plan resubmittals received | | | 8/4/2009 | | |
Tisha Gallop
|
|
|
received four copies if application, three copies of submittal documents and plan sheets FP-1; additional one copy of sheets FP-1 & FP-2 for reference only; taken to Fire review
|
Plan assigned to (Tim) | 8/4/2009 | | 8/4/2009 | | DONE |
Tim Frost
|
|
|
8/4/2009 13:22:06 TRF - activity updated through activity FIRA22 from case FIR09-00457.
|
Sprinkler Plan Check | 8/4/2009 | | 8/4/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
Plan assigned to (Tim) | 8/4/2009 | | 8/4/2009 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 8/4/2009 | | DONE |
|
|
|
t/c w brodie at ###-#### - permit denied - needs to be picked up and resubmitted
|
Miscellaneous action | | | 8/3/2009 | | DONE |
Tisha Gallop
|
|
|
gave denied plans to customer
|
Plan assigned to (Tim) | 7/27/2009 | | 7/29/2009 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 7/29/2009 | | 7/29/2009 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 7/29/2009 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 7/29/2009 | | DONE |
Tim Frost
|
|
|
Emailed review comments to Treasure Valley Fire Protection
|
Telephone call | | | 7/29/2009 | | DONE |
|
|
|
t/c w brodie at ###-#### - permit denied - needs to be picked up and resubmitted
|
Application received | | | 7/27/2009 | | |
|
|
|
|
Pending Assignment by SAM | 7/27/2009 | | 7/27/2009 | | DONE |
Tisha Gallop
|
|
|
7/27/2009 16:11:52 LEG - activity updated through activity FIRA158 from case FIR09-00457.
|