Permit Information
Permit NumberFIR09-00463
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 7031 S EISENMAN RD
Project NamePOWERBAR
Customer Number 
ePlanReview 
Description
Quick Permit
Relocating and adding 6 sprinklers to accomodate new wall and ceiling configurations.

(POWER BAR) Permit is for an existing tenant to remodel open office area to a 204 square foot conference room and to convert an existing office to divide a different office in half to create a uniform storage area. Approval per approved plans on file. Work to include: construction of interior non-bearing walls to create a conference room and a uniform storage room, installation of new lighting, new sink and counter (individual employee work area), new ducts and diffusers, new doors and hardware, and interior finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/4/20099/4/20099/4/2009APASS
DetailsForrest France
Fire sprinkler permit work passed final inspection.
INSP-Final Inspection9/1/20099/3/20099/3/2009ACANC
DetailsForrest France
Overbooked
INSP-Final Inspection8/17/20098/18/20098/18/2009AFAIL
DetailsTroy Cobbley
Inspection was for a rough-in since the ceiling tile had not been installed. One hanger on the upper level needs to be attached to the top chord of the truss instead of the bottom chord. Also Tim Frost is ok with the extended coverage head being used for 10' x 10' spacing. Piping is ok to cover.
Telephone call  8/18/2009 DONE
Spoke with Rick at Viking. He indicated the above sprinklers are spaced at 20'x20' ordinary hazard 2. The new area is a light hazard area. I told him that it was ok to use the same spacing of 20'x20' in this area since the sprinklers are approved for that distance and the hazard classification is less.
Application received  7/29/2009  
Sprinkler Plan Check7/29/2009 7/29/2009 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  7/29/2009 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  7/29/2009 DONE
DetailsTim Frost
Inspection Record Card- Fire7/29/2009 7/29/2009 DONE
Details
Telephone call  7/29/2009 DONE
Details
t/c w george at ###-#### - permit ready and fees given
Permit Ready to Issue  7/29/2009 DONE
Details
Issue and Print Permit  7/29/2009 DONE
Pending Assignment by SAM7/29/2009