Miscellaneous action | | | 3/8/2010 | | DONE |
|
|
|
Plans sent to scanning.
|
INSP-Final Inspection | 2/23/2010 | 2/24/2010 | 2/24/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Forward flush passed.
|
INSP-Final Inspection | 2/23/2010 | 2/23/2010 | 2/23/2010 | P | NR |
Forrest France
|
|
|
Partial inspection- Noted three obstructed pendent heads- one each at a storage room, isolation room, and detox room, need to complete forward flow test, missing the cover at the flow switch, two curtains at the womens sleep room are not installed, project related fire alarm permit is not yet finaled- however sprinkler riser monitoring tested okay.
|
INSP-Sprinkler Rough-in/Hydro | 2/17/2010 | 2/17/2010 | 2/17/2010 | A | PASS |
Troy Cobbley
|
|
|
Overhead hydro test passed.
|
INSP-Sprinkler Rough-in | 2/1/2010 | 2/1/2010 | 2/1/2010 | P | PASS |
Troy Cobbley
|
|
|
The sprinkler piping above the gridded areas can be covered except for the small room with a grid ceiling in the west end of the building.
|
INSP-Sprinkler Rough-in | 12/30/2009 | 12/30/2009 | 12/30/2009 | P | PASS |
Troy Cobbley
|
|
|
See the lasted version of the city approved plans for additional areas where the hardlid ceilings can be installed and cover the sprinkler piping.
|
Issue and Print Permit | | | 12/29/2009 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 12/28/2009 | | DONE |
|
|
|
t/c w trent at ###-#### - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 12/28/2009 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 12/15/2009 | 12/16/2009 | 12/16/2009 | A | PASS |
Troy Cobbley
|
|
|
See the city approved plans for additional rooms where piping is approved for cover. I spoke to the sprinkler fitter Scott and the project superintendant with EKC about the need for the plans to be resubmitted and the possibility of a stop work order if piping was covered in rooms that had not been approved for cover. All parties agreed the plans would be resubmitted immediately.
|
Inspection | 12/11/2009 | 12/11/2009 | 12/11/2009 | A | DONE |
Troy Cobbley
|
|
|
See the city approved plans for locations where the hardlids can be installed. These are the only locations where piping was inspected. Plans need to be resubmitted for approval that reflect the actual installation. Additional fitting have been installed, pipe re-routed and pipe sizing has been changed.
|
Issue and Print Permit | | | 10/22/2009 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 9/10/2009 | | 10/16/2009 | | DONE |
Tim Frost
|
|
|
10/16/2009 14:21:22 TRF - activity updated through activity FIRA22 from case FIR09-00494.
|
Plan resubmittals received | | | 10/16/2009 | | |
Tisha Gallop
|
|
|
received three copies of application, submittal documents and plan sheets 1 & 2; taken to Fire Review
|
Plan assigned to (Tim) | 10/16/2009 | | 10/16/2009 | | DONE |
Tim Frost
|
|
|
10/16/2009 14:21:22 TRF - activity updated through activity FIRA22 from case FIR09-00494.
|
Sprinkler Plan Check | 10/16/2009 | | 10/16/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/16/2009 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 10/16/2009 | | 10/16/2009 | | DONE |
|
|
|
|
Telephone call | | | 10/16/2009 | | DONE |
|
|
|
t/c w trent at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 10/16/2009 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 9/29/2009 | | 9/30/2009 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 9/30/2009 | | 9/30/2009 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
Miscellaneous action | | | 9/30/2009 | | DONE |
|
|
|
Emailed Review
|
Telephone call | | | 9/30/2009 | | DONE |
|
|
|
t/c w trent at ###-#### - permit denied - needs to be picked up and resubmitted
|
Plan resubmittals received | | | 9/29/2009 | | |
Tisha Gallop
|
|
|
received three copies of application, submittal documents and plan sheets 1 & 2; taken to fire review
|
Plan resubmittals received | | | 9/23/2009 | | DONE |
|
|
|
received 4 resubmitted fire applications and 3 sets of plans sent to Tim Frost in fire.
|
Plan assigned to (Tim) | 9/23/2009 | | 9/23/2009 | | DONE |
Tim Frost
|
|
|
09-29-09 Resub
|
Sprinkler Plan Check | 9/23/2009 | | 9/23/2009 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
Miscellaneous action | | | 9/23/2009 | | |
Tim Frost
|
|
|
Emailed review to Trent
|
Telephone call | | | 9/23/2009 | | DONE |
|
|
|
t/c w trent at ###-#### - permit denied - needs to be picked up and resubmitted
|
Telephone call | | | 9/10/2009 | | DONE |
|
|
|
left vm for trent at ###-#### - permit denied - needs to be picked up and resubmitted
|
Plan assigned to (Tim) | 8/18/2009 | | 9/10/2009 | | DONE |
Tim Frost
|
|
|
9/10/2009 10:36:31 TRF - activity updated through activity FIRA22 from case FIR09-00494.
|
Sprinkler Plan Check | 9/10/2009 | | 9/10/2009 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 8/20/2009 | | FAIL |
Tim Frost
|
|
|
|
Application received | | | 8/18/2009 | | |
|
|
|
|