Miscellaneous action | | | 1/6/2010 | | DONE |
|
|
|
Fire alarm plans taken to records for scanning.
|
INSP-Final Inspection | 12/16/2009 | 12/16/2009 | 12/16/2009 | P | PASS |
Forrest France
|
|
|
Fire alarm permit final approved.
|
INSP-Alarm Testing | 12/16/2009 | 12/16/2009 | 12/16/2009 | P | PASS |
Forrest France
|
|
|
Correction item field verified for compliance, inspection passed.
|
INSP-Final Inspection | 12/9/2009 | 12/11/2009 | 12/11/2009 | A | FAIL |
Forrest France
|
|
|
All correction notice items are finished with the exception of one HVAC unit which failed to shutdown upon smoke detection.
|
INSP-Final Inspection | 11/6/2009 | 11/6/2009 | 11/9/2009 | P | PART |
Forrest France
|
|
|
See notes dated 11/5.
|
INSP-Final Inspection | 11/2/2009 | 11/5/2009 | 11/5/2009 | A | PART |
Forrest France
|
|
|
Items needed for final include knox box installation, post signage at the door to the room containing the FACP, provide a lock at the circut breaker to the panel, post a map at the panel indicating locations of initiating devices and addresses/zones, one duct detector (#2) needs to be retested for unit shutdown as HVAC controls could not be initiated. See fire code review notes items # 21,22 and 23. Remainder of fire alarm work passed inspection and site testing.
|
Issue and Print Permit | | | 9/2/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 8/20/2009 | | 8/27/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
8/27/2009 10:23:56 SLC - activity updated through activity FIRA24 from case FIR09-00503.
|
1st review completed | | | 8/27/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 8/27/2009 | | 8/27/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 8/27/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Inspection Record Card- Fire | 8/27/2009 | | 8/27/2009 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 8/27/2009 | | DONE |
|
|
|
|
Telephone call | | | 8/27/2009 | | DONE |
|
|
|
Called Dave Whiting permit ready and fee fiven.
|
Application received | | | 8/20/2009 | | |
|
|
|
|