Permit Information
Permit NumberFIR09-00511
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 8300 W EMERALD ST
Project NameREI
Customer Number 
ePlanReview 
Description
This quick permit is to install new duct detectors and a pull station and connect them to the existing fire alarm system. This permit does not include notification. There are no written comments. Associated building permit: BLD09-01272 (REI - Mechanical Unit Replacement) Permit is to replace old roof top mechanical units and install additional structural support. Approval per approved plans on file and attached structural engineering. Work to include: installation of new ducts and diffusers, replacement of 5 roof top mechanical units, electrical upgrades, installation of new structural reinforcement, and installation of additional gas piping. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. This permit will require the new smoke detection system to be interconnected with the existing alarm system and an alarm permit form Boise City Fire Dept. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/1/2009 DONE
Fire alarm plans taken to records for scanning
INSP-Final Inspection9/10/20099/11/20099/11/2009APASS
DetailsTroy Cobbley
Permit finaled. The duct smoke detectors have been removed from the supply side of the hvac units by the mechanical contractor and the duct smoke detectors have been removed off of the hvac unit located in northeast corner of the building. This unit was rated at 1850cfm per the mechanical contractor.
INSP-Final Inspection9/4/20099/8/20099/8/2009AFAIL
DetailsTroy Cobbley
The hvac unit in the northeast corner of the building has two duct smoke detectors that are not connected to the existing fire alarm system as required per IFC 907.12. There is also a hvac unit located in the center of the building that has a duct smoke detector located on the supply side that is not connected to the existing fire alarm system as per IFC 907.12. The remaining units tested ok for shutdown and reported to the central station. A re-inspection fee is being added for the upcoming fourth inspection.
INSP-Final Inspection9/3/20099/4/20099/4/2009AFAIL
DetailsTroy Cobbley
The hvac units did not shutdown when the duct smoke detector went into alarm. A re-inspection fee for the next inspection, the third, has been applied.
INSP-Final Inspection9/2/20099/3/20099/3/2009PFAIL
DetailsTroy Cobbley
I left a message with the fire alarm contractor at 12:30 that I was headed towards the project site for the inspection. I left at 1:00 after no contact other than the store manager. No inspection was performed.
Permit Ready to Issue  8/28/2009 DONE
Inspection Record Card- Fire8/28/2009 8/28/2009 DONE
DetailsBarbara Stitt
Telephone call  8/28/2009 DONE
DetailsBarbara Stitt
Left voice message for Ken Webster that permit is ready and fees due///8-28-09 @ 8:20AM BAS
Issue and Print Permit  8/28/2009 DONE
Plan assigned to (Stephanie)8/26/2009 8/27/2009 DONE
DetailsStephanie L. Cobbley
8/27/2009 10:34:54 SLC - activity updated through activity FIRA24 from case FIR09-00511.
1st review completed  8/27/2009 DONE
Alarm Plan Check8/27/2009 8/27/2009 PASS
DetailsStephanie L. Cobbley
Quick permit - no written comments
PLANS TAKEN FRONT DESK ALARM  8/27/2009 DONE
Approved plans available at front counter
Telephone call  8/26/2009 DONE
Dave asked if we could expidite this submittal. He stated the owner did not know the duct detectors had to be tied in to the existing fire alarm system. I told dave that although it wasn't submitted in the approved format, that due to the permit scope of work we could review this as a quick permit. He understood that this was not the norm and that under other circumstances I would not be able to make these same accomodations.
Application received  8/26/2009