Permit Information
Permit NumberFIR09-00547
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 7311 W POTOMAC DR
Project NameBOISE POLICE ASSOCIATION
Customer Number 
ePlanReview 
Description
This fire alarm permit is to use the existing fire alarm panel, but replace all existing devices with new.
This permit scope includes a full manual system, notification devices, and HVAC shutdown.
Associated building permit: BLD09-00614 (BOISE POLICE ASSOCIATION - CLUBHOUSE AND
EVENT CENTER) A fire sprinkler system is required to be installed throughout this building. To
convert an existing 13,087 square foot office building (12,437 square feet inside and 650 square feet
outside) to an event center. The basement has a total floor area of about 6,227 square feet and the 1st
story has a total floor area of about 6,860 square feet (6,210 square feet inside and 650 square feet
outside). The work is to include 4 restrooms accessible to the disabled, an interior bearing wall in the
basement with a new concrete footing, altered open web floor trusses to shorten their span, two glu-lam
roof beams, a tube steel column, and interior finishes. Special inspection is required for welding and for
the modifications to the open web floor trusses. The work is required to comply with the approved
drawings, with the plan review report, and with all applicable codes and ordinances. In conjunction with
this permit, this building is required to be fully fire sprinklered per NFPA 13 as regulated by the Fire
Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/26/200910/26/200910/27/2009PPASS
DetailsTroy Cobbley
Permit finaled. Programming for the duct smoke detector needed to be modified while I waited. EOL voltage calculations checked out.
Miscellaneous action  10/27/2009 DONE
Fire alarm plans taken to records
Plan assigned to (Stephanie)9/11/2009 9/23/2009 DONE
DetailsStephanie L. Cobbley
9/23/2009 09:27:15 SLC - activity updated through activity FIRA24 from case FIR09-00547.
1st review completed  9/23/2009 DONE
PLANS TAKEN FRONT DESK ALARM  9/23/2009 DONE
Approved red lined plans available at the front counter.
Inspection Record Card- Fire9/23/2009 9/23/2009 DONE
DetailsBarbara Stitt
Permit Ready to Issue  9/23/2009 DONE
Telephone call  9/23/2009 DONE
DetailsBarbara Stitt
Left a voice message for Robert Gobler that permit is ready & fees due///9-23-09 @ 10:31am BAS
Issue and Print Permit  9/23/2009 DONE
Application received  9/11/2009  
Alarm Plan Check9/23/2009   PASS
Please see review comments and red lined plans.