Miscellaneous action | | | 2/26/2010 | | DONE |
|
|
|
fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 1/28/2010 | 1/29/2010 | 1/29/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The smoke detectors/sounder bases in the resident rooms did not have temporal tone until Guy changed the cadence programming to sound in temporal. A NetCon 5 was available.
|
INSP-Final Inspection | 1/25/2010 | 1/26/2010 | 1/26/2010 | P | FAIL |
Troy Cobbley
|
|
|
The NetCon reading for the AES panel was only 6 so no testing was performed. I did a conference/walk through with Guy and found two strobes in the north and south corridors to be overspaced but if the candellas are raised they will meet code for room spacing requirements. Also a 110cd strobe in the Handi-cap room is located too close to the ceiling. It will need to be changed to a 177cd or be lowered be 24" or more from the ceilign as per NFPA 72 sleeping area visula requirements. The manual pull station in the fire sprinkler riser room was mounted too high but Guy lowered it while I was on site. The location of all of the other a/v's were veriified and appear ok.
|
Inspection Record Card- Fire | 1/25/2010 | | 1/25/2010 | | DONE |
|
|
|
|
Telephone call | | | 1/25/2010 | | DONE |
|
|
|
t/c w lori at ###-#### - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 1/25/2010 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 1/25/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 1/20/2010 | | 1/22/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
1/22/2010 16:22:12 SLC - activity updated through activity FIRA24 from case FIR09-00549.
|
Alarm Plan Check | 1/22/2010 | | 1/22/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
plan modification passed with redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 1/22/2010 | | DONE |
|
|
|
approved redlined plan modification plans available at front counter
|
Plan assigned to (Stephanie) | 1/7/2010 | | 1/22/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
1/22/2010 16:22:12 SLC - activity updated through activity FIRA24 from case FIR09-00549.
|
Plan resubmittals received | | | 1/20/2010 | | |
|
|
|
Plan Modification: received application - calculation sheet - 2 sets of sheets F-1, F-2; taken to fire review
|
Alarm Plan Check | 1/11/2010 | | 1/11/2010 | | FAIL |
Stephanie L. Cobbley
|
|
|
Previous review comments and redlines were not addressed.
|
Telephone call | | | 1/11/2010 | | DONE |
|
|
|
Informed Lori w/ Alarmco that the plan modification would need to be rejected because previous issues were not addressed. She understands that all previous comments and redlines will need to be incorporated along with the plan modification prior to calling for a final inspection.
|
Plan resubmittals received | | | 1/7/2010 | | |
Tisha Gallop
|
|
|
*Application package recieved by SJA*
Received resubs for plan modification; received applications and two sets of submittal folders and plan sheets F-1, F-2; taken to fire review.*LEG*
|
Alarm Plan Check | 1/5/2010 | | 1/5/2010 | | FAIL |
Stephanie L. Cobbley
|
|
|
Spoke with Lori @ Alarmco. She indicated there would be more changes to the plan modification and decided the best steps to take would be to reject this review and resubmit a plan modification when all of the changes can be incorporated.
|
Plan resubmittals received | | | 1/4/2010 | | |
Tisha Gallop
|
|
|
Plan Modification: received application and submittal folder; taken to fire review
|
FIR-Aging Inspection | 12/25/2009 | 12/25/2009 | 12/29/2009 | | NR |
Troy Cobbley
|
|
|
Work is in progress
|
Issue and Print Permit | | | 9/25/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 9/14/2009 | | 9/23/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
9/23/2009 09:47:32 SLC - activity updated through activity FIRA24 from case FIR09-00549.
|
1st review completed | | | 9/23/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 9/23/2009 | | 9/23/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
Please see redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 9/23/2009 | | DONE |
|
|
|
Approved redlined plans available at the front counter.
|
Override - People Holds | | | 9/23/2009 | | |
|
|
|
|
Inspection Record Card- Fire | 9/23/2009 | | 9/23/2009 | | DONE |
Barbara Stitt
|
|
|
|
Override - People Holds | | | 9/23/2009 | | |
|
|
|
|
Permit Ready to Issue | | | 9/23/2009 | | DONE |
|
|
|
|
Telephone call | | | 9/23/2009 | | DONE |
Barbara Stitt
|
|
|
Called Laurie with Alarmco and told her that permit is ready & fees due///9-23-09 @ 10:39am BAS
|
Application received | | | 9/14/2009 | | |
|
|
|
|