Miscellaneous action | | | 10/27/2009 | | DONE |
|
|
|
Fire alarm plans taken to records
|
INSP-Final Inspection | 10/2/2009 | 10/2/2009 | 10/2/2009 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. One existing a/v is overspaced in exiting area and will remain that way until a remodel. One existing 15cd strobe in an existing corridor with a new wall wsa changed, while I waited, to a 110cd strobe. EOL drop was verified on this circuit.
|
Application received | | | 10/1/2009 | | |
|
|
|
|
Plan assigned to (Stephanie) | 10/1/2009 | | 10/1/2009 | | DONE |
|
|
|
|
1st review completed | | | 10/1/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 10/1/2009 | | 10/1/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit - No written comments
|
PLANS TAKEN FRONT DESK ALARM | | | 10/1/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 10/1/2009 | | 10/1/2009 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 10/1/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/1/2009 | | DONE |
|
|
|
|