Miscellaneous action | | | 9/20/2010 | | DONE |
|
|
|
FA plans taken to records for scanning.
|
INSP-Final Inspection | 9/7/2010 | 9/8/2010 | 9/8/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Telephone call | | | 9/3/2010 | | DONE |
|
|
|
Rob Ahten with Protex called regarding the required map indicating an updated/current plan showing the intiating devices. He wanted to know if he was required to provide it even if he did not modify any intiating devices. I let him know that, yes, it would be his responsibility and also pointed to the note on the review comments for this project that indicated as such. He stated confusion over other projects he said he has not had to do this on. I let him know that in years passed, we have only required an updated map if initiating devices were being modified in the scope of work. But, I let him know that in recent years, the fire department has had trouble with older buildings not having updated maps and that the response times have been hindered. They (the fire department) have requested that every fire alarm permit (regardless of initiating devices being affected or not) address the map being updated. I informed Rob that he should just count on, for every fire alarm permit, updating the map.
|
INSP-Final Inspection | 9/1/2010 | 9/2/2010 | 9/2/2010 | A | FAIL |
Troy Cobbley
|
|
|
As-builts in the format required were not provided.
|
Miscellaneous action | | | 2/23/2010 | | DONE |
|
|
|
Sent an email to Protex letting them know they will need to submit a plan modification prior to calling for an inspection. The plan modification will need to include as-built information, implement previous redlines and review comments, show any/all door holders and their connections to the fire alarm panel, existing horns in areas where walls have been removed or added, and any documentation affected by the changes. This is not an all inclusive list.
|
INSP-Final Inspection | 10/20/2009 | 10/21/2009 | 10/21/2009 | A | PART |
Troy Cobbley
|
|
|
The phase I area fire alarm testing is complete. The first visit I found missing a/v's and incorrect candella settings. At the second visit these items had been corrected. As-builts will be required prior to final sign off showing the a/v changes.
|
INSP-Final Inspection | 10/20/2009 | 10/20/2009 | 10/20/2009 | P | CANC |
Troy Cobbley
|
|
|
Rafe with Protex is the contact. His no. is ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Shawna Gates Inspection cancelled from web by: Shawna Gates
|
Issue and Print Permit | | | 10/14/2009 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/13/2009 | | 10/13/2009 | | DONE |
|
|
|
|
Telephone call | | | 10/13/2009 | | DONE |
|
|
|
t/c w mike at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 10/13/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 10/7/2009 | | 10/12/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
10/12/2009 15:17:47 SLC - activity updated through activity FIRA24 from case FIR09-00601.
|
1st review completed | | | 10/12/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 10/12/2009 | | 10/12/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 10/12/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Application received | | | 10/7/2009 | | |
|
|
|
|