Miscellaneous action | | | 2/26/2010 | | DONE |
|
|
|
fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 2/10/2010 | 2/10/2010 | 2/10/2010 | P | PASS |
Forrest France
|
|
|
Fire alarm permit final approved.
|
INSP-Final Inspection | 2/9/2010 | 2/9/2010 | 2/9/2010 | P | PART |
Forrest France
|
|
|
Correction notice items verified for completion, remainder of alarm work passed site testing. Final pending offsite monitoring check via permit FIR09-00740. Contractor to provide missing signage at the door to the FACP room.
|
INSP-Final Inspection | 2/5/2010 | 2/5/2010 | 2/9/2010 | P | NR |
Forrest France
|
|
|
Pending modifications per previous inspection- not ready 2/5 per phone call from contractor.
|
INSP-Final Inspection | 2/4/2010 | 2/4/2010 | 2/4/2010 | P | FAIL |
Forrest France
|
|
|
Smoke detectors at three locations are too close to HVAC diffusers, missing one SD address D1-13, HVAC units must shut down immediately upon duct smoke activation. Fire sprinkler riser supervision tested okay, five MP stations, battery trouble, open circuts, and notification circuts all passed functional testing. Offsite monitoring to be verified under project related FIR permit inspection. Plan resubmittals verified.
|
Plan assigned to (Stephanie) | 1/29/2010 | | 2/3/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
2/3/2010 11:50:07 SLC - activity updated through activity FIRA24 from case FIR09-00608.
|
Plan resubmittals received | | | 2/3/2010 | | |
Tisha Gallop
|
|
|
supplemental plans: received two copies of battery calcs, plan sheet E3.0 and riser diagram; taken to fire review
|
Alarm Plan Check | 2/3/2010 | | 2/3/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
plan modification approved
|
PLANS TAKEN FRONT DESK ALARM | | | 2/3/2010 | | DONE |
|
|
|
plan modification approved plans available at front counter
|
Inspection Record Card- Fire | 2/3/2010 | | 2/3/2010 | | DONE |
|
|
|
|
Telephone call | | | 2/3/2010 | | DONE |
|
|
|
t/c w stu at ###-#### - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 2/3/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/3/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/29/2010 | | |
Tisha Gallop
|
|
|
Plan modification: Received two copies of application, submittal folder and plan sheets E3.0, E4.0, (no number sheet); taken to Fire Review.
|
Issue and Print Permit | | | 11/17/2009 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/3/2009 | | 11/3/2009 | | DONE |
|
|
|
|
Telephone call | | | 11/3/2009 | | DONE |
|
|
|
t/c w stu at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 11/3/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 10/15/2009 | | 11/2/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
11/2/2009 15:53:55 SLC - activity updated through activity FIRA24 from case FIR09-00608.
|
Telephone call | | | 11/2/2009 | | DONE |
|
|
|
Spoke with Rob Ahten and let him know there were still several deficiencies in the plans, however, I gave him the option of me rejecting the plans now so he can correct the issues and only pay one review fee or I could approve them as-noted with the understanding he would need to resubmit a plan modification prior to calling for a final inspection, thus paying an additional review fee. He opted for getting the plans approved with noted now and submitting a plan modification prior to calling for a final inspection.
|
Alarm Plan Check | 11/2/2009 | | 11/2/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
A plan modification will need to be submitted implementing all notes, corrections, and field modifications prior to calling for a final inspection.
|
PLANS TAKEN FRONT DESK ALARM | | | 11/2/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Plan resubmittals received | | | 10/29/2009 | | |
Tisha Gallop
|
|
|
received two copies of application, submittal docs, and plan sheets E3.0, E4.0, and 1 sheet no pg#. Taken to Fire Review.
|
1st review completed | | | 10/21/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 10/21/2009 | | 10/21/2009 | | FAIL |
Stephanie L. Cobbley
|
|
|
see redlined plans and review comments
|
Miscellaneous action | | | 10/21/2009 | | DONE |
|
|
|
Faxed comments to Protex at their request. Tried to fax comments to the installing contractor but the number provided is not a valid number. Will try to call the phone number provided to let them know the plans have been failed.
|
Telephone call | | | 10/21/2009 | | DONE |
|
|
|
Left a message for Stu Welton at Snake River Electric letting him know the plans have been denied and that the fax number provided was not a valid number. I let him know that the review comments are available on the city website, but if he had any additional questions to feel free to give me a call. I then left my contact information.
|
Miscellaneous action | | | 10/21/2009 | | DONE |
Tisha Gallop
|
|
|
picked up rejected plans
|
Application received | | | 10/15/2009 | | |
|
|
|
|