Miscellaneous action | | | 2/26/2010 | | DONE |
|
|
|
fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 1/22/2010 | 1/22/2010 | 1/22/2010 | P | PASS |
Forrest France
|
|
|
Correction notice items verified for completion, as-built drawings recieved. Final fire alarm inspection passed, permit final approved.
|
INSP-Final Inspection | 12/29/2009 | 12/31/2009 | 12/31/2009 | A | FAIL |
Forrest France
|
|
|
Flow switches at risers #4 and 5 did not function, outside bell did not operate, provide weatherproof devices at the shower rooms, post a listing of account activity with today's date for signals sent at next inspection, provide record drawings indicating field modifications/address changes etc. Remainder of items tested okay include heat and smoke detectors, nac panels, EOL's, relay for mag locks, notification throughout, risers 1thru 3.
|
INSP-Final Inspection | 12/24/2009 | 12/29/2009 | 12/29/2009 | A | PART |
Forrest France
|
|
|
Duct detectors at the new production area passed testing, mag lock at the main entry/exit needs repair, coordinated notification testing for 12/31 per discussion.
|
INSP-Final Inspection | 12/24/2009 | 12/28/2009 | 12/28/2009 | A | PART |
Forrest France
|
|
|
Completed testing for duct detectors at areas A , F and mezzanines, retest DD at area D tool crib and area B office passed, incorrect sample tube orientation at AHU 28 fixed while on site, manual pull stations throughout tested okay, tamper switches at the sprinkler riser okayed, need to verify correct test orfice sizes at riser manifold prior to flow switch testing, two duct detectors at the Jenny Craig production line lacking access due to floor finishes underway, verified missing a/v has been installed at area D warehouse, relay for mag locks at the main entry is not ready for testing per contractor.
|
INSP-Final Inspection | 12/23/2009 | 12/24/2009 | 12/24/2009 | A | PART |
Forrest France
|
|
|
Completed duct detector testing at the production areas- see plan sheets areas E and F for annotations, incorrect sample tube orientation at address 16 repaired while on site.
|
INSP-Final Inspection | 12/18/2009 | 12/23/2009 | 12/23/2009 | A | FAIL |
Forrest France
|
|
|
Completed functional testing of duct detectors at office areas A and B, HVAC unit at the NW corner office area "A" failed to shut down (address 92), obstructed vent tubes at two locations repaired while on site, see plans for devices tested to date, discussed inspection schedule, noted some previous c/n items are incomplete.
|
INSP-Final Inspection | 12/18/2009 | 12/22/2009 | 12/22/2009 | A | PART |
Forrest France
|
|
|
Completed satisfactory testing of duct detectors in areas D and C with the exception of one HVAC unit (address 58) which failed to shut down upon smoke detector activation.
|
INSP-Final Inspection | 12/18/2009 | 12/21/2009 | 12/21/2009 | A | FAIL |
Forrest France
|
|
|
Missing one notification appliance at the warehouse Area C, one cd setting at the ramp is incorrect, need access to the laundry room and company store for functional testing, notification at some areas including the tool crib and mixing room appears to be obstructed, non-functional existing FA system devices to be removed. Two duct detectors at area C warehouse passed testing.
|
INSP-Final Inspection | 12/16/2009 | 12/18/2009 | 12/21/2009 | A | FAIL |
Forrest France
|
|
|
Items noted during initial walkthrough include: mag locks at the main entry need interconnected to the fire alarm system, one overspaced manual pull station, notification appliances at five locations have insufficient candella settings including the tech. services room, one conference room, sanitation room, one office NW corner per red line review comments, and the new mixing room, strobes at the west hall office area are overspaced, missing signage at the FACP room door, missing a notification appliance at the reimelt room, noted several existing fire alarm devices connected to the old panel in need of removal as they are no longer functional, stamped drawings do not indicate FACP and security panel interconnection, lacking notification coverage at the shower areas in both the womens and mens locker rooms.
|
Issue and Print Permit | | | 11/3/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 10/29/2009 | | 10/30/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
10/30/2009 13:25:38 SLC - activity updated through activity FIRA24 from case FIR09-00622.
|
1st review completed | | | 10/30/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 10/30/2009 | | 10/30/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 10/30/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Inspection Record Card- Fire | 10/30/2009 | | 10/30/2009 | | DONE |
|
|
|
|
Telephone call | | | 10/30/2009 | | DONE |
|
|
|
t/c w ken at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 10/30/2009 | | DONE |
|
|
|
|
Application received | | | 10/29/2009 | | |
|
|
|
|