Miscellaneous action | | | 12/3/2009 | | DONE |
|
|
|
FA plans taken to records for scanning
|
INSP-Final Inspection | 11/3/2009 | 11/4/2009 | 11/4/2009 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
|
Plan assigned to (Stephanie) | 10/30/2009 | | 11/2/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
11/2/2009 09:01:24 SLC - activity updated through activity FIRA24 from case FIR09-00624.
|
1st review completed | | | 11/2/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 11/2/2009 | | 11/2/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit - no written comments
|
PLANS TAKEN FRONT DESK ALARM | | | 11/2/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 11/2/2009 | | 11/2/2009 | | DONE |
|
|
|
|
Telephone call | | | 11/2/2009 | | DONE |
|
|
|
left vm for lori at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 11/2/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/2/2009 | | DONE |
|
|
|
|
Application received | | | 10/30/2009 | | |
|
|
|
|