Miscellaneous action | | | 9/20/2010 | | DONE |
|
|
|
FA plans taken to records for scanning.
|
INSP-Final Inspection | 9/7/2010 | 9/8/2010 | 9/8/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 9/1/2010 | 9/3/2010 | 9/3/2010 | A | FAIL |
Troy Cobbley
|
|
|
Provide approved map with all required information and mount at the facp.
|
Telephone call | | | 9/3/2010 | | DONE |
|
|
|
Rob Ahten with Protex called regarding the required map indicating an updated/current plan showing the intiating devices. He wanted to know if he was required to provide it even if he did not modify any intiating devices. I let him know that, while the comment was not on the comments for this particular permit, that it is on permit FIR10-00013. I let him know it would be his responsibility. He stated confusion over other projects he said he has not had to do this on. I let him know that in years passed, we have only required an updated map if initiating devices were being modified in the scope of work. But, I let him know that in recent years, the fire department has had trouble with older buildings not having updated maps and that the response times have been hindered. They (the fire department) have requested that every fire alarm permit (regardless of initiating devices being affected or not) address the map being updated. I informed Rob that he should just count on, for every fire alarm permit, updating the map.
|
CHANGE STATUS TO (ISS) | | | 9/1/2010 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/1/2010 | | 9/1/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 9/1/2010 | | DONE |
|
|
|
t/c w mike at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 9/1/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 8/24/2010 | | 8/31/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
8/31/2010 15:09:54 SLC - activity updated through activity FIRA24 from case FIR09-00635.
|
Alarm Plan Check | 8/31/2010 | | 8/31/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
plan modification approved
|
PLANS TAKEN FRONT DESK ALARM | | | 8/31/2010 | | DONE |
|
|
|
Approved plan modification documents available at front counter
|
Plan resubmittals received | | | 8/24/2010 | | DONE |
Tisha Gallop
|
|
|
plan mod rec'd 2 sets
|
Miscellaneous action | | | 6/1/2010 | | DONE |
|
|
|
A scope of work modification was allowed via email with the understanding it would be included in the plan modificaiton prior to final inspection. See attached document showing the changes. This is due to remodeling no longer being done in the areas of phasees10,11,&12.
|
INSP-Alarm Testing | 5/14/2010 | 5/14/2010 | 5/14/2010 | P | DONE |
Troy Cobbley
|
|
|
Fire sprinkler risers #2 and #3 inspected today. Flow switches and tamper switches functioned correctly. These items are not shown on the fire alarm plans and will need to be included when the plan modifications are submitted prior to a final sign off.
|
INSP-Alarm Testing | 4/20/2010 | 4/21/2010 | 4/20/2010 | A | CANC |
Troy Cobbley
|
|
|
If possible could we get before 8:00am. Nick is the contact his no. is ###-####. Thank you. Inspection requested from web by: Shawna Gates Phone #: ###-#### Inspection cancelled from web by: Shawna Gates
|
INSP-Alarm Testing | 4/19/2010 | 4/20/2010 | 4/19/2010 | A | CANC |
Troy Cobbley
|
|
|
Nick is the contact his no. is ###-####. Inspection requested from web by: Shawna Gates Phone #: ###-#### Inspection cancelled from web by: Shawna Gates
|
INSP-Alarm Testing | 4/15/2010 | 4/16/2010 | 4/15/2010 | A | CANC |
Troy Cobbley
|
|
|
Nick is the onsite contact his no. is ###-####. Thank you. Inspection requested from web by: Shawna Gates Phone #: ###-#### Inspection cancelled from web by: Shawna Gates
|
INSP-Alarm Testing | 3/23/2010 | 3/24/2010 | 3/24/2010 | A | PASS |
Troy Cobbley
|
|
|
The lobby area horn/strobes of phase 6 functioned correctly.
|
INSP-Alarm Testing | 3/22/2010 | 3/23/2010 | 3/23/2010 | A | PASS |
Troy Cobbley
|
|
|
The phase 8 existing fire alarm horns operated. We found that the new a/v's in the main lobby had not been inspected or connected to the NAC panel.
|
INSP-Alarm Testing | 12/3/2009 | 12/3/2009 | 12/3/2009 | P | DONE |
Troy Cobbley
|
|
|
Phase 4 fire alarm installation and testing is complete.
|
INSP-Final Inspection | 12/2/2009 | 12/3/2009 | 12/3/2009 | A | FAIL |
Troy Cobbley
|
|
|
This inspection is for phase 4. One additional horn/strobe needs to be installed as per the approved plans. Also horn only devices were not installed in the right hand corridor system of phase 4 as per the plans. Either re-install the horns or provide code compliant coverage through out the entire space served by the corridor system which includes the Lobby area.
|
Issue and Print Permit | | | 11/17/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 11/5/2009 | | 11/10/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
11/10/2009 08:35:12 SLC - activity updated through activity FIRA24 from case FIR09-00635.
|
1st review completed | | | 11/10/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 11/10/2009 | | 11/10/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See review comments and redlines
|
PLANS TAKEN FRONT DESK ALARM | | | 11/10/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Inspection Record Card- Fire | 11/10/2009 | | 11/10/2009 | | DONE |
|
|
|
|
Telephone call | | | 11/10/2009 | | DONE |
|
|
|
left vm for mike at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 11/10/2009 | | DONE |
|
|
|
|
Application received | | | 11/5/2009 | | |
|
|
|
|