Permit Information
Permit NumberFIR09-00641
StatusFinaled
Name ALARM STAR
Site Address 10139 W OVERLAND RD
Project NameSpring Creek - Bldg D
Customer Number 
ePlanReview 
Description
PLAN MODIFICATION: 2/26/10
This plan modification is to incorporate the previous review comments and redlines, as well as provide as-built conditions. Since the previous review, relays for access control and door holders have been added.


This fire alarm permit is to provide a new manual and automatic fire alarm system in a new building. Permit scope to include smoke detection, pull stations (as noted), heat detector, notification, and sprinkler system, hood suppression system, & HVAC monitoring.


Associated building permit: BLD09-00244 Spring Creek Overland - Senior Assisted-Living - Building D - Project consists of construction and finish of a 26,506 sq. ft., 42 sleeping unit, 50 bed, Senior Assisted Living Development with support facilities and associated site work, all per reviewed plans. To construct 18 one bedroom @ 552 sq. ft.; 12 Large Studio units @ 384 sq. ft.; 6 Small Studio Units @ 300 sq. ft.; and 6 Private HC units @ 227 sq. ft., six fully accessible units and 36 Type 'B' accessible units. drs DRH08-00246 CUP08-00010
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  3/16/2010 DONE
Plans taken to records for scanning.
INSP-Final Inspection3/1/20103/1/20103/2/2010PPASS
DetailsTroy Cobbley
Permit finaled
CHANGE STATUS TO (ISS)  3/1/2010 DONE
DetailsTisha Gallop
Plan assigned to (Stephanie)2/22/2010 2/26/2010 DONE
DetailsStephanie L. Cobbley
2/26/2010 14:06:51 SLC - activity updated through activity FIRA24 from case FIR09-00641.
Alarm Plan Check2/26/2010 2/26/2010 PASS
DetailsStephanie L. Cobbley
Plan modification approved with redlines and review comments
PLANS TAKEN FRONT DESK ALARM  2/26/2010 DONE
approved redlined plans available at front counter
Inspection Record Card- Fire2/26/2010 2/26/2010 DONE
Details
Telephone call  2/26/2010 DONE
Details
t/c w rand at ###-#### - permit (plan mod) ready and fees given
Permit Ready to Issue  2/26/2010 DONE
Details
INSP-Alarm Testing2/22/20102/22/20102/22/2010PPART
DetailsTroy Cobbley
A temporary occupancy was given with Scott's permission until the as-built fire alarm plans have been reviewed, approved and any changes inspected. When this is done the permit can be finaled.
Plan resubmittals received  2/22/2010  
DetailsTisha Gallop
Plan modification: received application, data sheets and plan sheets FA-1, FA-2; taken to Fire Review
INSP-Alarm Testing2/19/20102/19/20102/19/2010PFAIL
DetailsTroy Cobbley
The testing and inspection is complete except for resubmittals showing all of the changes including wall mount a/v's and the additional common area smoke detectors/av's in the new "rehab" room. The door holder circuit and the hvac shutdown was repaired while I was on site.
INSP-Final Inspection2/18/20102/18/20102/18/2010PFAIL
DetailsTroy Cobbley
The FACP panel, phone line troubles, battery troubles, type 1 hood suppression system interconnection and the interconnections with the new fire alarm system passed. Also passed were the system smoke detectors located in the central wing. The system smoke detectors in the west wing did not function correctly due to one detector being smoked in a room activated the sounder base in a room across the hall. I let Micheal know that resubmittals will be required showing the additional door magnet interconnections.
INSP-Alarm Testing2/16/20102/16/20102/16/2010PCANC
DetailsTroy Cobbley
Cancelled per Michael or ###-#### Rand Phone #: ###-####
Issue and Print Permit  11/20/2009 DONE
Plan assigned to (Stephanie)11/10/2009 11/13/2009 DONE
DetailsStephanie L. Cobbley
11/13/2009 13:40:03 SLC - activity updated through activity FIRA24 from case FIR09-00641.
Telephone call  11/13/2009 DONE
Left a message for Rand at Alarm Star to get clarification on the sprinkler monitoring devices as well as the one-line symbols not being consistent with the floor plans.
1st review completed  11/13/2009 DONE
Alarm Plan Check11/13/2009 11/13/2009 PASS
DetailsStephanie L. Cobbley
See redlines and review comments
PLANS TAKEN FRONT DESK ALARM  11/13/2009 DONE
Approved redlined plans available at front counter
Inspection Record Card- Fire11/13/2009 11/13/2009 DONE
Details
Telephone call  11/13/2009 DONE
Details
left vm for rand at ###-#### - permit ready and fees given
Permit Ready to Issue  11/13/2009 DONE
Details
Case Summary  11/10/2009 DONE
Application received  11/10/2009