INSP-Final Inspection | 12/1/2009 | 12/2/2009 | 12/2/2009 | A | PASS |
Forrest France
|
|
|
Corrections field verified for compliance, hood suppression system functioned properly under test conditions, manual pull activated, permit finaled.
|
INSP-Final Inspection | 11/24/2009 | 11/25/2009 | 11/25/2009 | A | FAIL |
Forrest France
|
|
|
Activation of the suppression system failed to shunt power to the electrical outlets under the hood, also need to provide a junction box outside the agent cabinet for wiring connections. Manual pull has not been tested.
|
Application received | | | 11/19/2009 | | |
|
|
|
|
Issue and Print Permit | | | 11/19/2009 | | DONE |
|
|
|
|