Miscellaneous action | | | 2/26/2010 | | DONE |
|
|
|
fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 1/22/2010 | 1/28/2010 | 1/28/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The AES was reporting a trouble condition to the FACP as a supervisory but Steve fixed that while I was on site.
|
Issue and Print Permit | | | 11/23/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 11/19/2009 | | 11/20/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
11/20/2009 11:07:00 SLC - activity updated through activity FIRA24 from case FIR09-00665.
|
1st review completed | | | 11/20/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 11/20/2009 | | 11/20/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 11/20/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 11/20/2009 | | 11/20/2009 | | DONE |
Darla L Downs
|
|
|
|
Telephone call | | | 11/20/2009 | | DONE |
|
|
|
t/c w charlie at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 11/20/2009 | | DONE |
|
|
|
|
Application received | | | 11/19/2009 | | |
|
|
|
|