Miscellaneous action | | | 3/16/2010 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 3/4/2010 | 3/5/2010 | 3/5/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 3/4/2010 | 3/4/2010 | 3/4/2010 | P | FAIL |
Troy Cobbley
|
|
|
Provide a map at the facp as discussed, provide corrected address at the monitoring station, provide as-builts that show the manual pull and smoke detector combined on zone 1, with zone 2 as a tamper, zone three as a PIV and zone 4 as the flow switch. Change out the submittal data sheet for the AES panel from a model 7750 to the 7788 which was actually installed. NetCon was a 5. All other items are passed.
|
Alarm Plan Check | 2/5/2010 | | 2/5/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 2/5/2010 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 2/5/2010 | | 2/5/2010 | | DONE |
|
|
|
|
Telephone call | | | 2/5/2010 | | DONE |
|
|
|
t/c w lori at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 2/5/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/5/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 11/24/2009 | | 2/5/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
2/5/2010 08:21:52 SLC - activity updated through activity FIRA24 from case FIR09-00674.
|
Miscellaneous action | | | 1/11/2010 | | DONE |
|
|
|
Department supervisor has indicated to hold the fire alarm permit until the tenant submits for a building permit for occupancy and an additional permit for racking.
|
Telephone call | | | 1/11/2010 | | DONE |
|
|
|
Updated Alarmco that we are still waiting for the tenant to submit for a building permit and racking permit before we can proceed with the fire alarm review.
|
Telephone call | | | 12/7/2009 | | DONE |
|
|
|
Called Alarmco and spoke to Lori to let her know this project is currently on hold and I cannot yet approve the plans. This is due to the tenant not having a CofO, any racking permits, or other building permits required for occupancy. I let her know as soon as these items are addressed by the tenant, then I can get the plans reviewed. She stated she understood and asked that I keep her updated.
|
Plan resubmittals received | | | 12/3/2009 | | |
Tisha Gallop
|
|
|
received application and two copies of submittal folder and plan sheets F-1, F-2; taken to Fire review
|
1st review completed | | | 11/30/2009 | | DONE |
|
|
|
failed
|
Alarm Plan Check | 11/30/2009 | | 11/30/2009 | | FAIL |
Stephanie L. Cobbley
|
|
|
See redlines on submittals and plans
|
Telephone call | | | 11/30/2009 | | DONE |
|
|
|
Called Lori at Alarmco to let her know I would need to fail the plans.
|
Miscellaneous action | | | 11/30/2009 | | DONE |
|
|
|
Faxed review comments to Alarmco
|
Application received | | | 11/24/2009 | | |
|
|
|
|