INSP-Final Inspection | 5/7/2010 | 5/10/2010 | 5/10/2010 | A | PASS |
Forrest France
|
|
|
Temporary partition has been removed, fire sprinkler permit final approved.
|
INSP-Sprinkler Rough-in | 12/30/2009 | 12/31/2009 | 12/31/2009 | A | FAIL |
Forrest France
|
|
|
Existing heads outside the new production area wall to the south side are overspaced and were to be relocated per approved drawings, overhead modifications at the "green room" and adjacent control room are not included in the scope of work, noted one pendent sprinkler head at the green room is supplied by a drop with an in-line ball vavle with the handle removed, outside bell failed to operate, flow switches at risers #4 and 5 did not function. Celing cover okayed at the new sifting room and the jenny craig production area.
|
INSP-Sprinkler Rough-in/Hydro | 12/30/2009 | 12/30/2009 | 12/30/2009 | A | CANC |
Troy Cobbley
|
|
|
Rescheduled for tomorrow
|
INSP-Sprinkler Rough-in | 12/29/2009 | 12/30/2009 | 12/29/2009 | A | DEFR |
Forrest France
|
|
|
Need to schedule a rough-to-cover at Power Bar. Scott is the contact @ ###-####. Please call him at least 1 hour before inspection to ensure someone will be there. Your time and attention is appreciated. Phone #: ###-#### Internet Inspection Request from: Trent Bice
|
Plan assigned to (Tim) | 11/25/2009 | | 12/3/2009 | | DONE |
Tim Frost
|
|
|
12/3/2009 11:27:23 TRF - activity updated through activity FIRA22 from case FIR09-00675.
|
Sprinkler Plan Check | 12/3/2009 | | 12/3/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/3/2009 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 12/3/2009 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/3/2009 | | 12/3/2009 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 12/3/2009 | | DONE |
Barbara Stitt
|
|
|
Left a message for Trent Bice that permit is ready & fees due///12-3-09 @ 2:15pm BAS
|
Issue and Print Permit | | | 12/3/2009 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/2/2009 | | |
Tim Frost
|
|
|
rec'd 3 sets
|
Miscellaneous action | | | 12/1/2009 | | DONE |
|
|
|
Emailed comments to Trent
|
Sprinkler Plan Check | 12/1/2009 | | 12/1/2009 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 12/1/2009 | | DONE |
Tim Frost
|
|
|
|
Telephone call | | | 12/1/2009 | | DONE |
|
|
|
left message w michelle for trent at ###-#### - permit denied - needs to be picked up and resubmitted
|
Miscellaneous action | | | 12/1/2009 | | DONE |
Tisha Gallop
|
|
|
picked up denied plans
|
Application received | | | 11/24/2009 | | |
|
|
|
|
INSP-Final Inspection | 1/22/2010 | 1/25/2010 | | A | |
Forrest France
|
|
|
trent Phone #: ###-####
|