Miscellaneous action | | | 6/7/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 5/13/2010 | 5/14/2010 | 5/14/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
|
INSP-Final Inspection | 5/7/2010 | 5/13/2010 | 5/13/2010 | P | CANC |
Troy Cobbley
|
|
|
Troy, Please let me know an approximate time, so I can let the building occupants know. Thanks, Jason ###-####. Inspection requested from web by: Jason Minnick Phone #: ###-#### Inspection cancelled from web by: Jason Minnick
|
FIR-Aging Inspection | 4/23/2010 | 4/23/2010 | 4/23/2010 | | NR |
Troy Cobbley
|
|
|
I spoke to jason and he will try to schedule an inspection for next week
|
Plan assigned to (Stephanie) | 11/25/2009 | | 1/22/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
1/22/2010 08:46:46 SLC - activity updated through activity FIRA24 from case FIR09-00678.
|
Alarm Plan Check | 1/22/2010 | | 1/22/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
no written comments
|
PLANS TAKEN FRONT DESK ALARM | | | 1/22/2010 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 1/22/2010 | | 1/22/2010 | | DONE |
|
|
|
|
Telephone call | | | 1/22/2010 | | DONE |
|
|
|
left message w lisa for jason at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 1/22/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/22/2010 | | |
|
|
|
|
Plan resubmittals received | | | 1/19/2010 | | |
Tisha Gallop
|
|
|
received two copies of application, submittal folder and plan sheets S-1, E2.0F, FA-1; taken to fire review
|
1st review completed | | | 12/8/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 12/8/2009 | | 12/8/2009 | | FAIL |
Stephanie L. Cobbley
|
|
|
plans failed - no review comments. heat detectors are not allowed as a substitution for full area smoke detection to eliminate duct detectors. Resubmittal required.
|
Telephone call | | | 12/8/2009 | | DONE |
|
|
|
let Jason know he could come pick up the denied plans.
|
Telephone call | | | 11/25/2009 | | DONE |
|
|
|
Spoke with Jason to let him know code does not allow heat detectors to be used as open area smoke detection coverage in place of duct detectors for HVAC shutdown. He stated he would like to find a solution, so I let him know I would hold the plans until Tuesday (12/1/09). If at that time there is nothing that can be found to support using the heat detectors that I would need to reject the plans. He stated he understood.
|
Application received | | | 11/25/2009 | | |
|
|
|
|