Permit Information
Permit NumberFIR09-00678
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 2791 S VICTORY VIEW WAY
Project NameMATERIALS LAB - DUCT DET. REMV
Customer Number 
ePlanReview 
Description
This permit is to remove three existing duct detectors that are not required per the mechanical engineer as well as City of Boise Mech. inspector (see permit app with letters of verification). There are no written comments. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/7/2010 DONE
Plans taken to records for scanning.
INSP-Final Inspection5/13/20105/14/20105/14/2010APASS
DetailsTroy Cobbley
Permit finaled.
INSP-Final Inspection5/7/20105/13/20105/13/2010PCANC
DetailsTroy Cobbley
Troy, Please let me know an approximate time, so I can let the building occupants know. Thanks, Jason ###-####. Inspection requested from web by: Jason Minnick Phone #: ###-#### Inspection cancelled from web by: Jason Minnick
FIR-Aging Inspection4/23/20104/23/20104/23/2010 NR
DetailsTroy Cobbley
I spoke to jason and he will try to schedule an inspection for next week
Plan assigned to (Stephanie)11/25/2009 1/22/2010 DONE
DetailsStephanie L. Cobbley
1/22/2010 08:46:46 SLC - activity updated through activity FIRA24 from case FIR09-00678.
Alarm Plan Check1/22/2010 1/22/2010 PASS
DetailsStephanie L. Cobbley
no written comments
PLANS TAKEN FRONT DESK ALARM  1/22/2010 DONE
approved plans available at front counter
Inspection Record Card- Fire1/22/2010 1/22/2010 DONE
Details
Telephone call  1/22/2010 DONE
Details
left message w lisa for jason at ###-#### - permit ready and fees given
Permit Ready to Issue  1/22/2010 DONE
Details
Issue and Print Permit  1/22/2010  
Plan resubmittals received  1/19/2010  
DetailsTisha Gallop
received two copies of application, submittal folder and plan sheets S-1, E2.0F, FA-1; taken to fire review
1st review completed  12/8/2009 DONE
Alarm Plan Check12/8/2009 12/8/2009 FAIL
DetailsStephanie L. Cobbley
plans failed - no review comments. heat detectors are not allowed as a substitution for full area smoke detection to eliminate duct detectors. Resubmittal required.
Telephone call  12/8/2009 DONE
let Jason know he could come pick up the denied plans.
Telephone call  11/25/2009 DONE
Spoke with Jason to let him know code does not allow heat detectors to be used as open area smoke detection coverage in place of duct detectors for HVAC shutdown. He stated he would like to find a solution, so I let him know I would hold the plans until Tuesday (12/1/09). If at that time there is nothing that can be found to support using the heat detectors that I would need to reject the plans. He stated he understood.
Application received  11/25/2009