Permit Information
Permit NumberFIR09-00719
StatusFinaled
Name PEAK ALARM
Site Address 2728 S COLE RD
Project Name2728 S. COLE - AES
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace an existing dialer with a new FACP and an AES RF radio. The system will include a pull station and sprinkler system monitoring. No HVAC has been shown on the plans. Notification is not required, nor is part of this permit scope. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/26/2010 DONE
fire alarm plans taken to records for scanning
INSP-Final Inspection1/28/20101/29/20101/29/2010APASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing1/27/20101/28/20101/28/2010APASS
DetailsTroy Cobbley
Permit finaled. I stopped at this project several times and found that an external antenna was required to get the required NetCon 5 signal. Data input at the monitoring station had to change zone 2 tamper switches from trouble signals to super visory signals.
INSP-Final Inspection1/27/20101/27/20101/27/2010PCANC
DetailsTroy Cobbley
To be cancelled per Mike since there is no access to the fire alarm panel room.
Issue and Print Permit  1/20/2010 DONE
Plan assigned to (Stephanie)12/16/2009 12/30/2009 DONE
DetailsStephanie L. Cobbley
12/30/2009 08:42:14 SLC - activity updated through activity FIRA24 from case FIR09-00719.
Alarm Plan Check12/30/2009 12/30/2009 PASS
DetailsStephanie L. Cobbley
see review comments
PLANS TAKEN FRONT DESK ALARM  12/30/2009 DONE
approved plans available at front counter
Inspection Record Card- Fire12/30/2009 12/30/2009 DONE
Details
Telephone call  12/30/2009 DONE
Details
t/c w mike madsen at ###-#### - permit ready and fees given
Permit Ready to Issue  12/30/2009 DONE
Plan resubmittals received  12/23/2009  
DetailsTisha Gallop
received application and two copies of folder with submittal info and plan sheet FA00; taken to fire review
1st review completed  12/18/2009 DONE
Alarm Plan Check12/18/2009 12/18/2009 FAIL
DetailsStephanie L. Cobbley
AES shown to be used as the FACP which is against code requirements and is not allowed.
Telephone call  12/18/2009 DONE
Left Mary Froemke (designer) a message letting her know the plans would have to be denied.
Telephone call  12/18/2009 DONE
Spoke to Mike at Peak Alarm to let him know the plans were denied because the AES is shown to be used as the FACP which is against code requirements and is not allowed.
Miscellaneous action  12/18/2009 DONE
Faxed a statement to Mike at Peak Alarm with the reasons listed for why the plans failed.
Application received  12/16/2009