Miscellaneous action | | | 2/26/2010 | | DONE |
|
|
|
fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 2/4/2010 | 2/5/2010 | 2/5/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled.
|
INSP-Alarm Testing | 2/4/2010 | 2/5/2010 | 2/5/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled.
|
INSP-Final Inspection | 2/3/2010 | 2/4/2010 | 2/4/2010 | A | FAIL |
Troy Cobbley
|
|
|
No testing was performed since an additional horn/strobe was not installed as required by the resubmitted plans. Also the manual pull station, at the west exit, that was shown to be relocated exceeds 48" above the finish floor. Since this device has been modified it needs to meet the current code mounting heights. All other a/v's seem to be installed correctly. The devices were not tested for function or EOL verified.
|
Issue and Print Permit | | | 1/25/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 12/18/2009 | | 1/14/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
1/14/2010 08:37:23 SLC - activity updated through activity FIRA24 from case FIR09-00723.
|
Alarm Plan Check | 1/14/2010 | | 1/14/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments and redlines
|
PLANS TAKEN FRONT DESK ALARM | | | 1/14/2010 | | DONE |
|
|
|
approved redlined plans available at front counter
|
Inspection Record Card- Fire | 1/14/2010 | | 1/14/2010 | | DONE |
|
|
|
|
Telephone call | | | 1/14/2010 | | DONE |
|
|
|
left message w lisa for tim at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 1/14/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/11/2010 | | |
Stephanie L. Cobbley
|
|
|
rec'd 2 sets of plans
|
Case Summary | | | 12/29/2009 | | DONE |
|
|
|
|
1st review completed | | | 12/23/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 12/23/2009 | | 12/23/2009 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans are denied. See review comments and redlined plans
|
Miscellaneous action | | | 12/23/2009 | | DONE |
|
|
|
faxed review comments to installing contractor
|
Miscellaneous action | | | 12/23/2009 | | DONE |
|
|
|
denied plans available at front counter for pick up
|
Application received | | | 12/18/2009 | | |
|
|
|
|