Permit NumberFIR09-00728
StatusFinaled
Name MOUNTAIN ALARM
Site Address 4770 N SHAMROCK AVE
Project NameGUARDIAN ANGELS DAYCARE
Customer Number 
ePlanReview 
Description
5-27-10: PLAN MODIFICATION
This plan modification includes adding/relocating devices due to an adjustment of the originally submitted floor plan as well as incorporate redlines and review comments from the review dated 1-21-10.

1-21-10:This fire alarm permit is to provide a new manual and automatic fire alarm system for a re-built building. System to include smoke detection, pull stations, notification, and monitoring for HVAC. This building is not sprinklered. The fire alarm system signals report via an AES RF radio to the central station.
Associated building permit: BLD09-00323 (GUARDIAN ANGELS DAYCARE) 10-26-09 PLAN MODIFICATION ADDING FLOOR AREA; CREATE ADDITIONAL ROOM & RESTROOM; RELOCATING AND ADDING INTERIOR SUPPORT ROOMS; ADD EXTERIOR DOOR AND WINDOW; REDUCING OTHER WINDOW AREA; CHANGE METAL ROOF TO ARCHITECTURAL SHINGLES IN SOME LOCATIONS; MODIFY ENERGY CODE LIGHTING & ENVELOPE; MODIFY KITCHEN LAYOUT; ADD SMOKE ALARM MODIFICATION AND PROVIDE PREVIOUSLY DEFERRED SYUBMITTAL ITEMS. DRS To construct and finish a new 5,800 sq. ft. daycare facility on portions of a new and existing foundation with a 330 sq. ft. mezzanine as part of the floor area. Interior bearing and non-bearing walls to create common areas and classroom/activity rooms. Building has a fire alarm system. drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  7/28/2010 DONE
FA plans taken to records for scanning.
INSP-Final Inspection6/7/20106/8/20106/8/2010PPASS
DetailsTroy Cobbley
Permit finaled.
INSP-Final Inspection6/3/20106/4/20106/4/2010PFAIL
DetailsTroy Cobbley
The manual pull stations have been corrected. The gas still has not been turned on to the hvac units so they could not be tested and the fire alarm panel is showing a "COMM 1" trouble.
INSP-Final Inspection6/1/20106/2/20106/2/2010PFAIL
DetailsTroy Cobbley
All of the previous corrections have been made. All of the smoke detectors tested and reported as per plan. The manual pull stations tested ok but did not report per plan. Also the heat detector 001 in the closet kept reporting as a trouble even though it was not being tested. Also a Com trouble kept comming up. The duct smoke detectors could not be tested since the gas has not been turned on to the hvac units.
INSP-Final Inspection6/1/20106/1/20106/2/2010PCANC
DetailsTroy Cobbley
Cancelled due to time constraints. Rescheduled for tomorrow.
Plan assigned to (Stephanie)5/17/2010 5/27/2010 DONE
DetailsStephanie L. Cobbley
5/27/2010 07:19:56 SLC - activity updated through activity FIRA24 from case FIR09-00728.
Alarm Plan Check5/27/2010 5/27/2010 PASS
DetailsStephanie L. Cobbley
see redlines and review comments
PLANS TAKEN FRONT DESK ALARM  5/27/2010 DONE
approved redlined plans available at front counter
Inspection Record Card- Fire5/27/2010 5/27/2010 DONE
DetailsPatricia Smith
Telephone call  5/27/2010 DONE
t/c w rose at ###-#### - permit (plan mod) ready and fees given
Permit Ready to Issue  5/27/2010 DONE
Details
CHANGE STATUS TO (ISS)  5/27/2010 DONE
(F) Reprint permit  5/27/2010 DONE
Telephone call  5/26/2010 DONE
Called to let Brett know that the calcs are still not correct and requested a revised set.
Miscellaneous action  5/26/2010 DONE
Recieved revised calcs
Telephone call  5/25/2010 DONE
Spoke with Brett to see when he would be getting the revised calcs to me. He said it would be this afternoon.
Miscellaneous action  5/25/2010 DONE
recieved revised battery calculations via email.
Miscellaneous action  5/24/2010 DONE
Recieved new calcs and voltage drops per request, however they were not correct.
Telephone call  5/24/2010 DONE
Spoke to Brett to let him know the new calcs he sent did not have the correct quantities or values. He stated he would have a revise set to me as soon as possible
Telephone call  5/21/2010 DONE
Spoke to Brett and went over the plan device locations (a few of the smoke detector locations are not accurately shown). He asked if I would please cloud and redline the plans indicating the correct locations. I also asked Brett to please email me the battery calculations and voltage drops (they were omitted from the submittal packet).
Plan resubmittals received  5/17/2010 DONE
DetailsTisha Gallop
Plan Modification: received application, two folders and plan sheet FA-1; taken to Fire review
INSP-Final Inspection4/28/20104/28/20104/28/2010PFAIL
DetailsTroy Cobbley
Plans need to be resubmitted showing the wall layout changes which will require additional notification device/devices. Several smoke and heat detectors were located less than 3' from supply registers. One strobe on the second level was not set at the correct candella and was corrected while on site. Voltage drops were verified for both of the notification circuits and both circuits checked out ok. The Netcon was verified at a 5 multiple times. All other notication device locations are approved except as noted above due to wall changes.
INSP-Conference4/6/20104/7/20104/7/2010PDONE
DetailsTroy Cobbley
This conference was to discuss the placement of a manual pull station at the center east exit. The request was to place the pull station on a cabinet. That was declined. It was decided that the pull station would be place on the left side door frame, next to the refrigerator. Mounting height was also discussed.
INSP-Conference4/6/20104/8/20104/6/2010PCANC
DetailsTroy Cobbley
Bret Anderson- our office is in Nampa so please give us time to arrive on time to meet you. We will also be calling the contractor to be included in the meeting. Inspection requested from web by: Diane Turner Phone #: ###-#### Inspection cancelled from web by: Diane Turner
Override - Parcel Holds  1/22/2010  
Issue and Print Permit  1/22/2010 DONE
Alarm Plan Check1/21/2010 1/21/2010 PASS
DetailsStephanie L. Cobbley
see redlines and review comments
PLANS TAKEN FRONT DESK ALARM  1/21/2010 DONE
approved redlined plans available at front counter
Override - Parcel Holds  1/21/2010  
Inspection Record Card- Fire1/21/2010 1/21/2010 DONE
Details
Telephone call  1/21/2010 DONE
Details
left message w diane for bret at ###-#### - permit ready and fees given
Override - Parcel Holds  1/21/2010  
Permit Ready to Issue  1/21/2010 DONE
Details
Plan assigned to (Stephanie)12/21/2009 1/21/2010 DONE
DetailsStephanie L. Cobbley
1/21/2010 10:01:27 SLC - activity updated through activity FIRA24 from case FIR09-00728.
Plan resubmittals received  1/15/2010  
DetailsStephanie L. Cobbley
rec'd two copies of plans
Alarm Plan Check1/6/2010 1/6/2010 FAIL
DetailsStephanie L. Cobbley
Plans are being rejected due to the building dept. recieving a plan modification that is changing the square footage, adding restrooms etc. that will significantly change the fire alarm plans. I let Bret know that I did not do a review on this re-submittal, therefore the next review will not be considered the 3rd submittal, only the 2nd. He asked that I just discard the plans he re-submitted.
Plan resubmittals received  1/5/2010 DONE
1st review completed  12/29/2009 DONE
Alarm Plan Check12/29/2009 12/29/2009 FAIL
DetailsStephanie L. Cobbley
plans denied - see redlined plans and review comments
Telephone call  12/29/2009 DONE
spoke to Bret with Mountain Alarm to let him know the plans had failed.
Miscellaneous action  12/29/2009 DONE
Faxed review comments to contractor
Miscellaneous action  12/29/2009 DONE
DetailsTisha Gallop
picked up denied plans
Miscellaneous action  12/28/2009 DONE
Inspector T. Cobbley issued a stop work order due to the fire alarm contractor doing work without a permit
Application received  12/21/2009