Miscellaneous action | | | 9/20/2010 | | DONE |
|
|
|
FA plans taken to records for scanning.
|
INSP-Final Inspection | 9/7/2010 | 9/8/2010 | 9/8/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 9/7/2010 | 9/7/2010 | 9/7/2010 | P | FAIL |
Troy Cobbley
|
|
|
Rob and I went over the map requirements.
|
INSP-Final Inspection | 9/1/2010 | 9/3/2010 | 9/3/2010 | A | FAIL |
Troy Cobbley
|
|
|
Provide approved map with all required information and mount at the facp.
|
Telephone call | | | 9/3/2010 | | DONE |
|
|
|
Rob Ahten with Protex called regarding the required map indicating an updated/current plan showing the intiating devices. He wanted to know if he was required to provide it even if he did not modify any intiating devices. I let him know that, yes, it would be his responsibility and also pointed to the note on the review comments for this project that indicated as such, and that this permit did involve relocating a pull station. He stated confusion over other projects he said he has not had to do this on. I let him know that in years passed, we have only required an updated map if initiating devices were being modified in the scope of work. But, I let him know that in recent years, the fire department has had trouble with older buildings not having updated maps and that the response times have been hindered. They (the fire department) have requested that every fire alarm permit (regardless of initiating devices being affected or not) address the map being updated. I informed Rob that he should just count on, for every fire alarm permit, updating the map.
|
CHANGE STATUS TO (ISS) | | | 8/25/2010 | | DONE |
|
|
|
|
Telephone call | | | 8/18/2010 | | DONE |
|
|
|
Spoke with Rob with Protex and requested a meeting to go over inconsistencies between the originally submitted plans and the plan modification. He indicated he would meet with me this afternoon.
|
Meeting | | | 8/18/2010 | | DONE |
|
|
|
Met with Rob and determined it was submitted under the wrong permit. Also the plan modification did not reflect the actual installation or reflect the original review comments/redlines. This will require a re-submittal but under FIR09-00638 instead.
|
CHANGE STATUS TO (ISS) | | | 8/18/2010 | | DONE |
Tisha Gallop
|
|
|
change to Iss status per SLC
|
Miscellaneous action | | | 8/16/2010 | | DONE |
|
|
|
Recieved two sets of scaled drawings as requested for plan modification
|
Plan resubmittals received | | | 8/11/2010 | | |
Stephanie L. Cobbley
|
|
|
rec'd 2 sets
|
FIR-Aging Inspection | 4/21/2010 | 4/21/2010 | 4/21/2010 | | DONE |
Troy Cobbley
|
|
|
work is in progress
|
Inspection Record Card- Fire | 1/20/2010 | | 1/20/2010 | | DONE |
|
|
|
|
Telephone call | | | 1/20/2010 | | DONE |
|
|
|
left message w shanna for mike at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 1/20/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/20/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 1/13/2010 | | 1/19/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
1/19/2010 16:01:27 SLC - activity updated through activity FIRA24 from case FIR10-00013.
|
1st review completed | | | 1/19/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 1/19/2010 | | 1/19/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 1/19/2010 | | DONE |
|
|
|
approved redlined plans available at front counter
|
Application received | | | 1/13/2010 | | |
|
|
|
|
Plan assigned to (Stephanie) | 8/11/2010 | | | | |
Stephanie L. Cobbley
|
|
|
|