Miscellaneous action | | | 7/19/2010 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 4/28/2010 | 4/29/2010 | 4/29/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 4/22/2010 | 4/23/2010 | 4/23/2010 | A | CANC |
Troy Cobbley
|
|
|
ken Phone #: ###-####
|
INSP-Final Inspection | 4/14/2010 | 4/14/2010 | 4/14/2010 | P | FAIL |
Troy Cobbley
|
|
|
Permit will be ready to final when a fire alarm permit has been submitted for the new butterfly valve to be connected to the existing fire alarm system. I let the ken with American Fire and the PetsMart job superintendant that I would not final their permits until a fire alarm permit had been issued for this additional valve. This is due to the canopy permit, which this valve controls, being associated with the PetsMart permit.
|
INSP-Sprinkler Rough-in | 3/25/2010 | 3/26/2010 | 3/26/2010 | A | PASS |
Troy Cobbley
|
|
|
The sprinkler piping as marked on the plans can be covered. The through bolts for the earth quake bracing have been addressed.
|
INSP-Sprinkler Rough-in | 3/24/2010 | 3/25/2010 | 3/25/2010 | A | PART |
Troy Cobbley
|
|
|
The sprinkler piping rough-in is ok except for the lag bolts on the earthquake bracing attachments need to be changed to through bolts with the correct length and blocking as discussed. Could not make it back for a re-inspection/cover approval so Ken is scheduling for tomorrow morning.
|
Plan assigned to (Tim) | 1/13/2010 | | 1/14/2010 | | DONE |
Tim Frost
|
|
|
1/14/2010 09:03:44 TRF - activity updated through activity FIRA22 from case FIR10-00014.
|
Sprinkler Plan Check | 1/14/2010 | | 1/14/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are annotations on the plans.
|
1st review completed | | | 1/14/2010 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/14/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 1/14/2010 | | 1/14/2010 | | DONE |
|
|
|
|
Telephone call | | | 1/14/2010 | | DONE |
|
|
|
left message w vanessa for jim at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 1/14/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/14/2010 | | DONE |
|
|
|
|
Application received | | | 1/13/2010 | | |
|
|
|
|
Pending Assignment by SAM | 1/13/2010 | | 1/13/2010 | | DONE |
Patricia Smith
|
|
|
1/13/2010 13:29:27 P_S - activity updated through activity FIRA158 from case FIR10-00014.
|