Miscellaneous action | | | 7/19/2010 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 4/28/2010 | 4/29/2010 | 4/29/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 4/22/2010 | 4/23/2010 | 4/23/2010 | A | FAIL |
Troy Cobbley
|
|
|
The forward flush of the backflow passed. This permit can be finaled when the interconnections with the fire alarm system have been verified. Ken to provide copies of the test papers at the next inspection.
|
INSP-Sprinkler Rough-in/Hydro | 4/8/2010 | 4/9/2010 | 4/9/2010 | A | PASS |
Troy Cobbley
|
|
|
The overhead hydro test passed.
|
INSP-Sprinkler Rough-in/Hydro | 4/7/2010 | 4/8/2010 | 4/8/2010 | A | FAIL |
Troy Cobbley
|
|
|
Overhead hydro test failed due to pressure drop and visable leak.
|
INSP-Sprinkler Rough-in | 3/31/2010 | 4/1/2010 | 4/1/2010 | A | PASS |
Troy Cobbley
|
|
|
The piping above the layin tile in the west end of the building can be covered.
|
INSP-Sprinkler Rough-in/Hydro | 3/29/2010 | 3/29/2010 | 3/29/2010 | P | PASS |
Troy Cobbley
|
|
|
Sprinkler rough-in passed. The office areas on the south side of the building are ok for ceiling installation by this inspector. The office areas on the west end are not finished. I noted many heads that are still covered with tin foil to protect from painting. Resubmittals are required due to piping changes as marked in red on the city approved plans (riser nipples in the storage remote area are the biggest issue).
|
INSP-Final Inspection | 3/29/2010 | 3/29/2010 | 3/29/2010 | P | FAIL |
Troy Cobbley
|
|
|
Project is not ready for a final inspection. A rough-in inspection has been set up.
|
Sprinkler Plan Check | 1/27/2010 | | 1/27/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/27/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 1/27/2010 | | 1/27/2010 | | DONE |
|
|
|
|
Telephone call | | | 1/27/2010 | | DONE |
|
|
|
left vm for jim at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 1/27/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/27/2010 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 1/14/2010 | | 1/19/2010 | | DONE |
Tim Frost
|
|
|
1/19/2010 08:11:11 TRF - activity updated through activity FIRA22 from case FIR10-00018.
|
Sprinkler Plan Check | 1/19/2010 | | 1/19/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 1/19/2010 | | DONE |
Tim Frost
|
|
|
|
Plan assigned to (Tim) | 1/19/2010 | | 1/19/2010 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 1/14/2010 | | DONE |
Tim Frost
|
|
|
Requested additional information defining the commodity and the storage/packaging arrangement.
|
Application received | | | 1/14/2010 | | |
|
|
|
|
Pending Assignment by SAM | 1/14/2010 | | 1/14/2010 | | DONE |
Alexandra L. DeYoung
|
|
|
1/14/2010 13:59:56 ALR - activity updated through activity FIRA158 from case FIR10-00018.
|
Case Summary | | | 1/14/2010 | | DONE |
|
|
|
|