Permit Information
Permit NumberFIR10-00023
StatusFinaled
Name ALARMCO
Site Address 805 W FRANKLIN ST
Project NameFranklin Plaza
Customer Number 
ePlanReview 
Description
This quick permit is to relocate an existing notification device and provide a new one in a conference room due to a tenant improvement. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Devices to be mounted per 2007 NFPA 72 mounting and spacing requirements. There are no written comments. Associated building permit: BLD09-02003 (CRADLEPOINT - 2ND & 4TH FLOORS) 12/8/09 - PLAN MODIFICATION FOR 2ND & 4TH FLOORS. CHANGE ROOM LOCATIONS AND SIZES, RELOCATE LIGHT FIXTURES AND CONTROLS. RELOCATE EXIT SIGN AT SECOND FLOOR TO BE IN FRONT OF NEW VESTIBULE DOORS, CONSTRUCT NEW FUTURE EXIT VESTIBULE ON SECOND FLOOR. ORIGINAL CODE PLAN REVIEWS AND RED-LINED NOTES ON ORIGINAL PLANS ARE STILL APPLICABLE TO THIS PERMIT. DRS NOTE:1st floor T.I. will be under separate permit. This building is fully sprinklered to substitute for 1-hour construction. Construct interior non-bearing walls to create private offices, open work areas, conference rooms and support areas; upgrade electrical, mechanical, sprinkler and alarm systems; and interior floor and wall finishes. Upgrade of stairs enclosures for code compliance will be under separate permit, BLD09-02173. drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/26/2010 DONE
fire alarm plans taken to records for scanning
INSP-Final Inspection1/20/20101/22/20101/22/2010APASS
DetailsForrest France
Scope of fire alarm work passed field testing, permit finaled.
Plan assigned to (Stephanie)1/19/2010 1/20/2010 DONE
DetailsStephanie L. Cobbley
1/20/2010 08:10:42 SLC - activity updated through activity FIRA24 from case FIR10-00023.
1st review completed  1/20/2010 DONE
Alarm Plan Check1/20/2010 1/20/2010 PASS
DetailsStephanie L. Cobbley
quick permit - no written comments. See scope of work
PLANS TAKEN FRONT DESK ALARM  1/20/2010 DONE
approved plans available at front counter
Inspection Record Card- Fire1/20/2010 1/20/2010 DONE
Details
Telephone call  1/20/2010 DONE
Details
left message w leslie for mike at ###-#### - permit ready and fees given
Permit Ready to Issue  1/20/2010 DONE
Details
Issue and Print Permit  1/20/2010 DONE
Application received  1/19/2010