Miscellaneous action | | | 7/19/2010 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 2/23/2010 | 2/24/2010 | 2/24/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The extended coverage pendants have been moved to more than 8' apart.
|
INSP-Sprinkler Rough-in | 2/9/2010 | 2/10/2010 | 2/10/2010 | A | PART |
Troy Cobbley
|
|
|
The sprinkler piping can be covered. I noted that two of the new extended coverage pendants at the Lobby are less than 8' apart. The solution will be verified at the final inspection. The riser also has a current inspection tag.
|
Plan assigned to (Tim) | 1/21/2010 | | 1/22/2010 | | DONE |
Tim Frost
|
|
|
1/22/2010 09:35:40 TRF - activity updated through activity FIRA22 from case FIR10-00031.
|
Sprinkler Plan Check | 1/22/2010 | | 1/22/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 1/22/2010 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/22/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 1/22/2010 | | 1/22/2010 | | DONE |
|
|
|
|
Telephone call | | | 1/22/2010 | | DONE |
|
|
|
t/c w jeff anderson at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 1/22/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/22/2010 | | DONE |
|
|
|
|
Application received | | | 1/21/2010 | | |
|
|
|
|
Pending Assignment by SAM | 1/21/2010 | | 1/21/2010 | | DONE |
Patricia Smith
|
|
|
1/21/2010 11:19:15 P_S - activity updated through activity FIRA158 from case FIR10-00031.
|