Miscellaneous action | | | 6/7/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 5/6/2010 | 5/7/2010 | 5/7/2010 | A | PASS |
Forrest France
|
|
|
Correction items field verified, fire alarm passed final inspection.
|
INSP-Final Inspection | 5/6/2010 | 5/6/2010 | 5/6/2010 | P | CANC |
Forrest France
|
|
|
Forrest, Please call me and let me know when you can be onsite, so I can let everyone know. Thanks, Jason ###-#### Inspection requested from web by: Jason Minnick Phone #: ###-#### Inspection cancelled from web by: Jason Minnick
|
INSP-Final Inspection | 4/29/2010 | 5/3/2010 | 5/3/2010 | A | PART |
Forrest France
|
|
|
Final pending items including signage at the door the to FACP room, knox box install, hat flash in the elevator car upon SD or HD activation in the hoistway or machine room, pending drop ceiling install at the mechanical/electrical room or the addition of a post indicator valve for the fire sprinkler system may require field modifications to the alarm system. Remainder of FA work passed inspection.
|
Plan assigned to (Stephanie) | 2/10/2010 | | 2/11/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
2/11/2010 10:53:05 SLC - activity updated through activity FIRA24 from case FIR10-00057.
|
1st review completed | | | 2/11/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 2/11/2010 | | 2/11/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 2/11/2010 | | DONE |
|
|
|
approved redlined plans available at front counter
|
Inspection Record Card- Fire | 2/11/2010 | | 2/11/2010 | | DONE |
|
|
|
|
Telephone call | | | 2/11/2010 | | DONE |
|
|
|
t/c w jason at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 2/11/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/11/2010 | | DONE |
|
|
|
|
Application received | | | 2/10/2010 | | |
|
|
|
|