Miscellaneous action | | | 2/26/2010 | | DONE |
|
|
|
fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 2/19/2010 | 2/19/2010 | 2/19/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Plan assigned to (Stephanie) | 2/17/2010 | | 2/18/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
2/18/2010 13:25:12 SLC - activity updated through activity FIRA24 from case FIR10-00067.
|
1st review completed | | | 2/18/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 2/18/2010 | | 2/18/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit passed - no written comments
|
PLANS TAKEN FRONT DESK ALARM | | | 2/18/2010 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 2/18/2010 | | 2/18/2010 | | DONE |
|
|
|
|
Telephone call | | | 2/18/2010 | | DONE |
|
|
|
left vm for joe at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 2/18/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/18/2010 | | DONE |
|
|
|
|
Application received | | | 2/17/2010 | | |
|
|
|
|