Miscellaneous action | | | 7/19/2010 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 4/20/2010 | 4/20/2010 | 4/20/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 4/8/2010 | 4/8/2010 | 4/8/2010 | P | PASS |
Troy Cobbley
|
|
|
The remaining sprinkler piping can be covered.
|
INSP-Sprinkler Rough-in | 3/17/2010 | 3/18/2010 | 3/18/2010 | A | PASS |
Troy Cobbley
|
|
|
All hard lid areas are ok to cover. Additional sprinkler pendants are required to be installed, as per plan, in both window areas on both sides of the main entry. One side is a ceiling pocket that does not meet all of the requirements of NFPA 13 - 8.6.7 and the other side has blockage caused by a wall.
|
Plan assigned to (Tim) | 2/17/2010 | | 2/18/2010 | | DONE |
Tim Frost
|
|
|
2/18/2010 11:20:50 TRF - activity updated through activity FIRA22 from case FIR10-00071.
|
Sprinkler Plan Check | 2/18/2010 | | 2/18/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 2/18/2010 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/18/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 2/18/2010 | | 2/18/2010 | | DONE |
|
|
|
|
Telephone call | | | 2/18/2010 | | DONE |
|
|
|
left vm for brodie at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 2/18/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/18/2010 | | DONE |
|
|
|
|
Application received | | | 2/17/2010 | | |
|
|
|
|
Pending Assignment by SAM | 2/17/2010 | | 2/17/2010 | | DONE |
Alexandra L. DeYoung
|
|
|
2/17/2010 16:01:19 ALR - activity updated through activity FIRA158 from case FIR10-00071.
|