Miscellaneous action | | | 2/8/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 1/28/2011 | 2/1/2011 | 2/1/2011 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
(F) Reprint permit | | | 1/5/2011 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 1/5/2011 | | |
|
|
|
|
Plan assigned to (Stephanie) | 12/28/2010 | | 1/4/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 1/4/2011 | | 1/4/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved - see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 1/4/2011 | | DONE |
|
|
|
Approved plan modification plans available at front counter
|
Inspection Record Card- Fire | 1/4/2011 | | 1/4/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 1/4/2011 | | DONE |
|
|
|
t/c w charlie - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 1/4/2011 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/28/2010 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: received two copies of application, submittal binder and plans; taken to Fire review.
|
INSP-Final Inspection | 12/15/2010 | 12/16/2010 | 12/16/2010 | A | FAIL |
Troy Cobbley
|
|
|
The plans need to be re-submitted for plan modifications, as per the red note by the plan reviewer, since the partitions/shelves exceed 6'-0" in height. I went ahead and tested the smoke detectors which passed inspection.
|
FIR-Aging Inspection | 11/25/2010 | 11/25/2010 | 12/2/2010 | | NR |
Troy Cobbley
|
|
|
work is in progress
|
INSP-Sprinkler Rough-in | 5/14/2010 | 5/18/2010 | 5/18/2010 | A | PASS |
Troy Cobbley
|
|
|
The fire alarm in phase two passed inspection
|
INSP-Final Inspection | 4/8/2010 | 4/8/2010 | 4/8/2010 | P | PART |
Troy Cobbley
|
|
|
The phase 1 fire alarm testing is passed.
|
INSP-Sprinkler Rough-in | 4/6/2010 | 4/7/2010 | 4/7/2010 | A | FAIL |
Troy Cobbley
|
|
|
This inspectio was for phase 1. All items tested ok except for the duct detector located in the main existing exit corridor did not shut down the hvac unit when activated.
|
Issue and Print Permit | | | 3/1/2010 | | DONE |
|
|
|
|
1st review completed | | | 2/26/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 2/26/2010 | | 2/26/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
approved with redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 2/26/2010 | | DONE |
|
|
|
approved redlined plans available at front counter
|
Miscellaneous action | | | 2/26/2010 | | DONE |
|
|
|
recieved an email with a pdf document of the letter signed by the engineer.
|
Inspection Record Card- Fire | 2/26/2010 | | 2/26/2010 | | DONE |
|
|
|
|
Telephone call | | | 2/26/2010 | | DONE |
|
|
|
left vm for charlie at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 2/26/2010 | | DONE |
|
|
|
|
Telephone call | | | 2/25/2010 | | DONE |
|
|
|
Left a message for Charlie Bayne letting him know that the letter provided (stating compliance with design intent) was signed by an electrical designer, however a PE was listed as the designer on the permit applications. I stated that I either need a new letter signed by the engineer listed on the permit application, or the electrical designers qualifications (i.e. NICET cert., factory trained, etc...) need to be provided and he needs to be listed as the designer.
|
Telephone call | | | 2/25/2010 | | DONE |
|
|
|
Charlie returned my phone call and said that he would try to have the new letter to me by tomorrow.
|
Application received | | | 2/18/2010 | | |
|
|
|
|
Plan assigned to (Stephanie) | 2/18/2010 | | 2/18/2010 | | DONE |
Darla L Downs
|
|
|
|