INSP-Final Inspection | 3/8/2010 | 3/9/2010 | 3/9/2010 | P | PASS |
Forrest France
|
|
|
Scope of fire sprinkler system modifications completed satisfactory, permit finaled. NOTE: concealed space below the stage filled with non-combustible insulation to meet exceptions allowed per NFPA 13.
|
Issue and Print Permit | | | 3/8/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/2/2010 | | |
Tim Frost
|
|
|
rec'd 1 set
|
Sprinkler Plan Check | 3/2/2010 | | 3/2/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/2/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 3/2/2010 | | 3/2/2010 | | DONE |
|
|
|
|
Telephone call | | | 3/2/2010 | | DONE |
|
|
|
t/c w don at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 3/2/2010 | | DONE |
|
|
|
|
Telephone call | | | 2/26/2010 | | DONE |
Tim Frost
|
|
|
Spoke with Scott Beseman. Informed him that the area beneath the stage would have to have sprinklers or be completely filled with non combustible insulation.
|
Application received | | | 2/22/2010 | | |
|
|
|
|
Pending Assignment by SAM | 2/22/2010 | | 2/22/2010 | | DONE |
Patricia Smith
|
|
|
2/22/2010 12:06:32 P_S - activity updated through activity FIRA158 from case FIR10-00078.
|
Plan assigned to (Tim) | 2/22/2010 | | 2/22/2010 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 2/22/2010 | | 2/22/2010 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 2/22/2010 | | DONE |
Tim Frost
|
|
|
|
Telephone call | | | 2/22/2010 | | DONE |
|
|
|
t/c w don at ###-#### - permit denied - needs to be picked up and resubmitted
|