INSP-Final Inspection | 7/30/2010 | 8/2/2010 | 8/3/2010 | P | PASS |
Forrest France
|
|
|
Corrections verified, final walkthrough and acceptance testing passed. Permit finaled.
|
INSP-Sprinkler Rough-in | 7/13/2010 | 7/13/2010 | 7/13/2010 | A | PART |
Forrest France
|
|
|
Ref. inspection notes and correction list 6/30.
|
INSP-Sprinkler Rough-in/Hydro | 7/1/2010 | 7/2/2010 | 7/2/2010 | P | PART |
Forrest France
|
|
|
Concluded satisfactory 24hr. air test for the new dry system per NFPA 13.
|
INSP-Sprinkler Rough-in/Hydro | 7/1/2010 | 7/1/2010 | 7/1/2010 | P | PART |
Forrest France
|
|
|
Begin 24 hour pneumatic test for the new dry system at 1:00PM @ 42psig.
|
INSP-Sprinkler Rough-in | 6/30/2010 | 6/30/2010 | 6/30/2010 | P | FAIL |
Forrest France
|
|
|
Missing one lateral seismic brace at the south end of the dry system main, shadowing at one office area, welded 2" outlets on the dry system mains serving branchlines at the exterior canopy at some locations are not properly graded, noted one dry pendent at the main entry has been added. See stamped plans for annotations.
|
INSP-Sprinkler Rough-in/Hydro | 6/29/2010 | 6/30/2010 | 6/30/2010 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic test for both the wet and dry systems completed satisfactory.
|
INSP-Sprinkler Rough-in/Hydro | 6/28/2010 | 6/28/2010 | 6/28/2010 | P | DEFR |
Forrest France
|
|
|
john Phone #: ###-####
|
Issue and Print Permit | | | 4/19/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/12/2010 | | DONE |
|
|
|
received 3 sets of resubmittals sent to Tom Frost
|
Sprinkler Plan Check | 4/12/2010 | | 4/12/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/12/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 4/12/2010 | | 4/12/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 4/12/2010 | | DONE |
|
|
|
t/c w len at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/12/2010 | | DONE |
|
|
|
|
Miscellaneous action | | | 3/11/2010 | | DONE |
|
|
|
Emailed review
|
Plan assigned to (Tim) | 3/1/2010 | | 3/3/2010 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 3/3/2010 | | 3/3/2010 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 3/3/2010 | | DONE |
Tim Frost
|
|
|
|
Telephone call | | | 3/3/2010 | | DONE |
|
|
|
t/c w len at ###-#### - permit denied - needs to be picked up and resubmitted
|
Application received | | | 3/1/2010 | | |
|
|
|
|
Pending Assignment by SAM | 3/1/2010 | | 3/1/2010 | | DONE |
Alexandra L. DeYoung
|
|
|
3/1/2010 09:03:19 ALR - activity updated through activity FIRA158 from case FIR10-00089.
|