Permit NumberFIR10-00089
StatusFinaled
Name DELTA FIRE SYSTEMS
Site Address 1175 W LAKE HAZEL RD
Project NameOld Dominion Freight Lines
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of two systems, one dry loop protecting the dock and one wet tree system protection the office/sales area. The systems are supplied by approximately 160'± of 6" C-900 underground piping through a 4" backflow preventer and header. The dry system is designed to use galvanized piping.

Old Dominion Freight Lines - To construct a new 20,075 square foot, one story office and warehouse building and related site improvements. This building will be constructed on tilt-up concrete exterior walls and a pre-engineered metal building interior and roof structure. The warehouse will have a ten foot metal overhang over the loading dock areas. This building will be fully fire sprinkled. Office 3,700 square feet; Warehouse 16,375 square feet. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/30/20108/2/20108/3/2010PPASS
DetailsForrest France
Corrections verified, final walkthrough and acceptance testing passed. Permit finaled.
INSP-Sprinkler Rough-in7/13/20107/13/20107/13/2010APART
DetailsForrest France
Ref. inspection notes and correction list 6/30.
INSP-Sprinkler Rough-in/Hydro7/1/20107/2/20107/2/2010PPART
DetailsForrest France
Concluded satisfactory 24hr. air test for the new dry system per NFPA 13.
INSP-Sprinkler Rough-in/Hydro7/1/20107/1/20107/1/2010PPART
DetailsForrest France
Begin 24 hour pneumatic test for the new dry system at 1:00PM @ 42psig.
INSP-Sprinkler Rough-in6/30/20106/30/20106/30/2010PFAIL
DetailsForrest France
Missing one lateral seismic brace at the south end of the dry system main, shadowing at one office area, welded 2" outlets on the dry system mains serving branchlines at the exterior canopy at some locations are not properly graded, noted one dry pendent at the main entry has been added. See stamped plans for annotations.
INSP-Sprinkler Rough-in/Hydro6/29/20106/30/20106/30/2010APART
DetailsForrest France
Overhead hydrostatic test for both the wet and dry systems completed satisfactory.
INSP-Sprinkler Rough-in/Hydro6/28/20106/28/20106/28/2010PDEFR
DetailsForrest France
john Phone #: ###-####
Issue and Print Permit  4/19/2010 DONE
Plan resubmittals received  4/12/2010 DONE
received 3 sets of resubmittals sent to Tom Frost
Sprinkler Plan Check4/12/2010 4/12/2010 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  4/12/2010 DONE
DetailsTim Frost
Inspection Record Card- Fire4/12/2010 4/12/2010 DONE
DetailsPatricia Smith
Telephone call  4/12/2010 DONE
t/c w len at ###-#### - permit ready and fees given
Permit Ready to Issue  4/12/2010 DONE
Details
Miscellaneous action  3/11/2010 DONE
Emailed review
Plan assigned to (Tim)3/1/2010 3/3/2010 DONE
DetailsTim Frost
Sprinkler Plan Check3/3/2010 3/3/2010 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  3/3/2010 DONE
DetailsTim Frost
Telephone call  3/3/2010 DONE
Details
t/c w len at ###-#### - permit denied - needs to be picked up and resubmitted
Application received  3/1/2010  
Pending Assignment by SAM3/1/2010 3/1/2010 DONE
DetailsAlexandra L. DeYoung
3/1/2010 09:03:19 ALR - activity updated through activity FIRA158 from case FIR10-00089.