Permit Information
Permit NumberFIR10-00096
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 5207 W IRVING ST
Project NameKENNY'S ROD SHOP
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of protecting one new spray booth, associated stack and filter. There are also minor sprinkler additions and relocations due to new wall configuration. Sidewall sprinklers are to be installed below the garage doors. The existing was reported as design for Ordinary Hazard Group III .21/1568 + 250 with 125 sf maximum head spacing. The system demand was reported as 345.98 GPM @ 58.31 PSI

(KENNY'S ROD SHOP) Interior and exterior remodel to an existing 7,500 sq. ft. building for a new auto body shop tenant per approved plans. Work to include: perform select interior demolition; remove select existing doors, door frames, and walls; install new steel I-beams and posts; frame in existing wall openings; replace specific existing overhead doors with new; remove portions of the existing ceiling structure and framing as designated on plans; remove the existing exterior steel siding and replace with new panel system; and install a pre-manufactured "Spray Net - Side Draft Spray Paint Booth". All work per the approved plans, Engineering, attached plan review report, and all other reviewing agencies approvals. NOTE: This building is fully fire sprinklered for one-hour substitution. Any modifications or alterations to the existing sprinkler system WILL require a separate permit. CZC10-00001 per Planning and Zoning. **SRZ**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  7/19/2010 DONE
Sent to records for scanning.
INSP-Final Inspection4/12/20104/13/20104/13/2010APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro4/2/20104/5/20104/5/2010APASS
DetailsTroy Cobbley
The overhead hydro test passed and the earth quaking has been modified and trapeze hangers provided on the mains.
INSP-Sprinkler Rough-in3/29/20103/30/20103/31/2010APART
DetailsTroy Cobbley
The piping rough-in in general is passed. Trapeze hangers are required for the new 3" supply main since all of its weight is hanging from a single Z purlin and the earthquake bracing needs to be anchored at the beams as discussed with Roy. The overhead hydro test failed since a visable leak was found at a pendant and the 3" supply main had not been included in the test.
Issue and Print Permit  3/11/2010 DONE
Plan assigned to (Tim)3/5/2010 3/10/2010 DONE
DetailsTim Frost
3/10/2010 14:20:05 TRF - activity updated through activity FIRA22 from case FIR10-00096.
Plan resubmittals received  3/10/2010 DONE
received 1 checklist,3 paas and 4 plans sent to Tim F.
Sprinkler Plan Check3/10/2010 3/10/2010 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  3/10/2010 DONE
DetailsTim Frost
Inspection Record Card- Fire3/10/2010 3/10/2010 DONE
Details
Telephone call  3/10/2010 DONE
Details
t/c w bernie at ###-#### - permit ready and fees given
Permit Ready to Issue  3/10/2010 DONE
Details
Sprinkler Plan Check3/5/2010 3/5/2010 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  3/5/2010 DONE
DetailsTim Frost
Telephone call  3/5/2010 DONE
LM for John - permit is denied
Application received  3/5/2010