Permit Information
Permit NumberFIR10-00098
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 720 PARK BLVD Unit: 200
Project NameBMC WEST AT MK CENTRAL PLAZA 2
Customer Number 
ePlanReview 
Description
Scope
6-29-10 PLAN MODIFICATION:
This plan modification is to implement field changes as well as items from the original review.

3-15-10:
This fire alarm permit is to extend the existing fire alarm system into the new tenant space. This permit scope includes notification (voice evacuation), a new remote power supply to accommodate the visuals, and a smoke detector (non-required above the remote power supply). All new speakers are tapped at ΒΌ watt.

Associated building permit: BLD10-00338 (BMC SELECT - Washington Group Plaza - Ste# 200) Permit is to remodel an existing 25,348 square foot tenant space to accommodate the tenant's needs. Approval contingent upon adhering to the approved plans on file and obtaining the necessary Fire Alarm and Fire Sprinkler permits. Work to include: demolition of multiple enclosed offices to create more open office area, construction of interior non-bearing walls to create four new enclosed offices, installation of new accessible door hardware, installation of new doors and sidelights, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. Racking that exceeds 8 ft. in height requires a separate Building Permit be submitted and approved before installation. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  7/28/2010 DONE
FA plans taken to records for scanning.
INSP-Final Inspection7/23/20107/23/20107/23/2010PPASS
DetailsForrest France
Fire alarm permit final approved.
INSP-Alarm Testing7/15/20107/16/20107/16/2010PPASS
DetailsTroy Cobbley
Permit finaled. EOL was verified
Issue and Print Permit  7/15/2010 DONE
Alarm Plan Check6/29/2010 6/29/2010 PASS
DetailsStephanie L. Cobbley
Plan modification approved
PLANS TAKEN FRONT DESK ALARM  6/29/2010 DONE
Approved plan modification plans available at front counter
Inspection Record Card- Fire6/29/2010 6/29/2010 DONE
DetailsPatricia Smith
Telephone call  6/29/2010 DONE
left vm for john at ###-#### - permit (plan mod) ready and fees given
Permit Ready to Issue  6/29/2010 DONE
Details
Plan resubmittals received  6/28/2010 DONE
received1 application,1 submittal checklist,2 calcs,and 3 copies of sheet FAFP-1 sent to Stephanie Cobbley
INSP-Final Inspection6/8/20106/10/20106/10/2010PFAIL
DetailsForrest France
Missing notification at one conference room, one area lacks sufficient visual coverage, need to verify mag locks at the main entry release on fire alarm, RR coverage, and audibility at two storage rooms during the functional test as discussed. Noted one overspaced 75cd appliance at the SE corner.
INSP-Final Inspection6/2/20106/4/20106/4/2010PCANC
DetailsTroy Cobbley
Per Josh this inspection will be rescheduled for later since his and I's schedules are not going to work out.
Issue and Print Permit  3/17/2010 DONE
Plan assigned to (Stephanie)3/9/2010 3/15/2010 DONE
DetailsStephanie L. Cobbley
3/15/2010 11:52:29 SLC - activity updated through activity FIRA24 from case FIR10-00098.
1st review completed  3/15/2010 DONE
Alarm Plan Check3/15/2010 3/15/2010 PASS
DetailsStephanie L. Cobbley
see redlines and review comments
PLANS TAKEN FRONT DESK ALARM  3/15/2010 DONE
approved redlined plans available at front counter
Inspection Record Card- Fire3/15/2010 3/15/2010 DONE
Details
Telephone call  3/15/2010 DONE
t/c w john at ###-#### - permit ready and fees given
Permit Ready to Issue  3/15/2010 DONE
Details
Telephone call  3/10/2010 DONE
Spoke to John and requested information regarding the existing speaker circuit being added to. I let him know I need to know which panel the circuit is going to, what the watts used are, and how much that leaves available. He stated he would get it to me ASAP.
Application received  3/9/2010