Miscellaneous action | | | 7/28/2010 | | DONE |
|
|
|
FA plans taken to records for scanning.
|
INSP-Final Inspection | 7/23/2010 | 7/23/2010 | 7/23/2010 | P | PASS |
Forrest France
|
|
|
Fire alarm permit final approved.
|
INSP-Alarm Testing | 7/15/2010 | 7/16/2010 | 7/16/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. EOL was verified
|
Issue and Print Permit | | | 7/15/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 6/29/2010 | | 6/29/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved
|
PLANS TAKEN FRONT DESK ALARM | | | 6/29/2010 | | DONE |
|
|
|
Approved plan modification plans available at front counter
|
Inspection Record Card- Fire | 6/29/2010 | | 6/29/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 6/29/2010 | | DONE |
|
|
|
left vm for john at ###-#### - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 6/29/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 6/28/2010 | | DONE |
|
|
|
received1 application,1 submittal checklist,2 calcs,and 3 copies of sheet FAFP-1 sent to Stephanie Cobbley
|
INSP-Final Inspection | 6/8/2010 | 6/10/2010 | 6/10/2010 | P | FAIL |
Forrest France
|
|
|
Missing notification at one conference room, one area lacks sufficient visual coverage, need to verify mag locks at the main entry release on fire alarm, RR coverage, and audibility at two storage rooms during the functional test as discussed. Noted one overspaced 75cd appliance at the SE corner.
|
INSP-Final Inspection | 6/2/2010 | 6/4/2010 | 6/4/2010 | P | CANC |
Troy Cobbley
|
|
|
Per Josh this inspection will be rescheduled for later since his and I's schedules are not going to work out.
|
Issue and Print Permit | | | 3/17/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 3/9/2010 | | 3/15/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
3/15/2010 11:52:29 SLC - activity updated through activity FIRA24 from case FIR10-00098.
|
1st review completed | | | 3/15/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 3/15/2010 | | 3/15/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 3/15/2010 | | DONE |
|
|
|
approved redlined plans available at front counter
|
Inspection Record Card- Fire | 3/15/2010 | | 3/15/2010 | | DONE |
|
|
|
|
Telephone call | | | 3/15/2010 | | DONE |
|
|
|
t/c w john at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 3/15/2010 | | DONE |
|
|
|
|
Telephone call | | | 3/10/2010 | | DONE |
|
|
|
Spoke to John and requested information regarding the existing speaker circuit being added to. I let him know I need to know which panel the circuit is going to, what the watts used are, and how much that leaves available. He stated he would get it to me ASAP.
|
Application received | | | 3/9/2010 | | |
|
|
|
|